ATR 142
Controller / Regolatore
User manual / Manuale d’uso
Summary
1
2
3
4
5
6
7
8
Model Identification ........................................................................ 7
Technical Data .................................................................................. 7
2.1 General Features..................................................................... 7
2.2 Hardware Features................................................................. 8
2.3 Software Features .................................................................. 9
Dimensions and Installation ......................................................... 9
Electrical wirings ..........................................................................10
4.1 Wiring diagram.....................................................................10
Configuration EASYUP..................................................................14
Display and Keys Functions .........................................................15
6.1 Numeric Indicators (Display) .............................................15
6.2 Meaning of Status Lights (Led) .........................................15
6.3 Keys .......................................................................................16
Controller Functions......................................................................16
7.1 Modifying Main Setpoint and Alarm Setpoint Values.16
7.2 Auto-Tune ...............................................................................17
7.3 Manual Tuning......................................................................17
7.4 Automatic Tuning ...............................................................18
7.5 Soft Start.................................................................................18
7.6 Automatic/Manual Regulation for % Output Control 18
7.7 Pre-Programmed Cycle .......................................................19
7.8 Memory Card (optional) .....................................................20
7.9 Loading default values........................................................21
7.10 LATCH ON Functions............................................................22
7.11 Digital Input Functions .......................................................24
7.12 Dual Action Heating-Cooling ............................................25
Timer operation..............................................................................27
8.1 Single Timer ...........................................................................28
User manual - ATR 142 3
8.2
8.3
8.4
8.5
9
10
11
12
13
14
Dual Timer..............................................................................28
Dual Sequential Timer ........................................................29
Dual Timer Loop ..................................................................29
Relating Timers to Alarms .................................................30
Serial Communication ........................................................31
9.1 Slave .......................................................................................31
9.2 Master .....................................................................................36
9.2.1 Master Mode in retransmission .............................37
9.2.2 Master Mode Remote process................................39
Configuration .................................................................................39
10.1 Modify Configuration Parameter .....................................39
Table of Configuration Parameters ...........................................40
Alarm Intervention Modes ...........................................................55
Table of Anomaly Signals.............................................................59
Summary of Configuration parameters ...................................60
4 ATR 142 - User manual
Sommario
1
2
3
4
5
6
7
8
Identificazione del modello .........................................................64
Dati tecnici.......................................................................................64
2.1 Caratteristiche generali ......................................................64
2.2 Caratteristiche hardware ...................................................65
2.3 Caratteristiche software .....................................................66
Dimensioni e installazione ..........................................................66
Collegamenti elettrici ..................................................................67
4.1 Schema di collegamento....................................................67
Configurazione EASYUP ...............................................................71
Funzione dei visualizzatori e tasti ..............................................72
6.1 Indicatori numerici (display)..............................................72
6.2 Significato delle spie di stato (led) ....................................72
6.3 Tasti .......................................................................................73
Funzioni del regolatore ................................................................73
7.1 Modifica valore setpoint principale e setpoint di allarme.. 73
7.2 Auto-tune ...............................................................................74
7.3 Lancio del Tuning Manuale ...............................................74
7.4 Tuning Automatico .............................................................74
7.5 Soft Start.................................................................................75
7.6 Regolazione automatico/manuale per controllo % uscita .75
7.7 Ciclo pre-programmato......................................................76
7.8 Memory Card (opzionale) ..................................................77
7.9 Caricamento valori di default ...........................................78
7.10 Funzione LATCH ON .............................................................78
7.11 Funzioni da Ingresso digitale ............................................80
7.12 Funzionamento in doppia azione (caldo-freddo) ........81
Funzioni Timer ................................................................................83
8.1 Singolo Timer ........................................................................84
Manuale d’suo - ATR 142 5
9
10
11
12
13
14
8.2 Doppio Timer.........................................................................84
8.3 Doppio Timer Sequenziale .................................................85
8.4 Doppio Timer Loop ..............................................................86
8.5 Associazione Timer - Allarmi .............................................86
Comunicazione Seriale .................................................................88
9.1 Slave .......................................................................................88
9.2 Master .....................................................................................93
9.2.1 Modalità master in ritrasmissione........................93
9.2.2 Modalità master processo remoto .......................95
Configurazione ...............................................................................96
10.1 Modifica parametro di configurazione ...........................96
Tabella parametri di configurazione .........................................97
Modi d’intervento allarme ........................................................ 112
Tabella segnalazioni anomalie ............................................... 117
Promemoria configurazione .................................................... 118
6 ATR 142 - Manuale d’uso
Introduction
Thank you for choosing a Pixsys controller.
With the ATR142 model Pixsys makes available in a single device multiple options relevant to sensor input and actuators
command in addition to the extended power range 24…230
Vac/Vdc. With 17 sensors to select and outputs configurable
as relay or SSR command, the user or retailer can reduce
stock by rationalising investment and device availability. The
series includes a version equipped with serial communication
RS485 Modbus. The configuration is further simplified by the
Memory cards which are provided with internal battery and
therefore do not require cabling to power the controller.
1
Model Identification
Refer to the table below to easily select preferred model.
All versions available with power 24…230 Vac/Vdc +/-15%
50/60Hz – 4,6VA
ATR142-ABC
2 relays (8A+5A) + 1 SSR
ATR142-ABC-T
1 relays 8A + 1 Ssr + RS485
2
2.1
Technical Data
General Features
Display
Operating
temperature
Sealing
Material
4 0.40 inch displays + 4 0.30 displays
1 relays 8A + 1 Ssr + RS485
IP65 front panel (with gasket)
IP30 box, IP20 terminals
Polycarbonate UL94V2 self-extinguishing
User manual - ATR 142 7
Weight
2.2
100 g
Hardware Features
AN1. Configurable
via software.
Thermocouple type:
K, S, R, J. Automatic
compensation of cold
junction from 0°C to
Analogue 50°C.
Thermoresistance:
input
PT100, PT500, PT1000,
Ni100, PTC1K, NTC10K
(β 3435K). Linear: 0-10V,
0-20 or 4-20mA, 0-40mV
Potentiometers:
6KΩ, 150KΩ,
Relay
output
SSR
output
Supply
2 relays (ATR142-ABC)
1 relay (ATR142-ABC-T)
Configurable as
command and/or alarm
output
1 SSR Configurable as
command output and/
or alarm output.
Power supply
24..230 Vac/Vdc +/-15%
50/60Hz
8 ATR 142 - User manual
Tolerance (25°C)
+/-0.2 % ± 1 digit for
thermocouple input,
thermo- resistance and
V/mA.
Cold junction accuracy
0.1°C/°C
Impedance:
0-10V: Ri>110KΩ
0-20mA: Ri<5Ω
4-20mA: Ri<5Ω
0-40mV: Ri>1MΩ
Contacts:
Q1: 8A-250V~
for resistive loads
Q2: 5A-250V~
for resistive loads
12Vdc/30mA
Power consumption
4.6VA
2.3
Software Features
Regulation
ON-OFF with hysteresis.
algorithms
P, PI, PID, PD with proportional time
Proportional band 0...9999°C or °F
Integral time
0,0...999,9 sec (0 excluded)
Derivative time
0,0...999,9 sec (0 excluded)
Manual or automatic Tuning, configurable
alarms, protection of command and alarm
setpoints, activation of functions via
digital input, preset cycle with Start/Stop.
Controller
functions
Dimensions and Installation
3
Frontal panel cut-out
Dima di foratura
28.5 x 70.5 mm
Suggested thickness
Spessore suggerito
2 ÷ 8 mm
Guarnizione per 32x74
Cod. 1600.00.082 (optional)
Gasket for 32x74
Memory Card (optional)
Cod. MEMORY 2100.30.005
42mm
inserimento
Memory Card
PIXSYS
42mm
insert
Memory Card
1
CN1
6
Memory Card (optional)
with battery
Cod. MEMORY 2100.30.003
U1
C1
6
35 mm
CN1
2
1
1
3
77 mm
7
53 mm
User manual - ATR 142 9
Electrical wirings
4
Although this controller was designed to resist
electromagnetic interferences in industrial environments, pease observe following safety guidelines:
• Separate the feeder line from the power lines.
• Avoid placing near units with remote control switches,
electromagnetic contactors, high powered motors and in
all instances use specific filters.
• Avoid placing near power units, particularly if phase controlled.
Wiring diagram
4.1
PIXSYS
PIXSYS
ATRxxx-xx
2 wire
ATRxxx-xxT
2 wire
4/20mA
Power
3A 230V
Cosf 0.8
1A 230V
Cosf 0.8
Q1
SUPPLY
7
8
9
10
11
SUPPLY
Tc
-
12
1
1
Memory
ATR142-ABC
2
Q1
3
4
+VDC PTC/NTC
RS485
5
6
SSR
-
7
8
9
10
11
Memory
ATR142-ABC-T
Power Supply
2
24...230V
AC/DC
1
Switching power supply with extended
range
24…230 Vac/dc ±15% 50/60Hz – 5,5VA.
10 ATR 142 - User manual
Tc
+
6
+
5
+
4
+
3
-
PT/NI100/1K
3A 230V
Cosf 0.8
+
2
+
1
+VDC PTC/NTC
SSR
1
V/I
10A 23a0V
Cosf 1
PT/NI100/1K
Q2
+
-
V/I
-
+
5A 230V
Cosf 1
+
10A 230V
Cosf 1
4/20mA
I
I
Power
12
-
11
AN1 Analogue Input
For thermocouples K, S, R, J.
• Comply with polarity
• For possible extensions, use
Shield/Schermo
compensated cable and terminals
suitable for the thermocouples
used(compensated)
• When shielded cable is used, it should
be grounded at one side only
For thermoresistances PT100, NI100
Shield/Schermo • For the three-wire connection use
A
wires with the same section
• For the two-wire connection shortB
circuit terminals 10 and 12
• When shielded cable is used, it should
be grounded at one side only
C
Tc
+
12
11
PT/NI100
10
12
RED 10
WHITE 11
RED 12
Shield/Schermo
11
PTC/NTC
10
For thermoresistances NTC, PTC,
PT500, PT1000 e potentiometers
• When shielded cable is used, it should
be grounded at one side only to avoid
ground loop currents
9
+VDC
10
Shield/Schermo
-
11
V/I
+
12
For linear signals V/mA
• Comply with polarity
• When shielded cable is used, it should
be grounded at one side only
User manual - ATR 142 11
Examples of Connection for linear input
12
For signals 0….10V
• Comply with polarity
0...10V
11
12
For signals 0/4….20mA with three-wire
sensor
• Comply with polarity
C = Sensor output
B = Sensor ground
A = Sensor power
C
0/4...20mA
11
B
9
A
PRESSURE TRANSMITTER
SENSORE DI PRESSIONE
12
C
For signals 0/4..20mA with external
power of sensor
• Comply with polarity
C = Sensor output
B = Sensor ground
0/4...20mA
11
B
EXTERNAL SUPPLY
ALIMENTAZIONE ESTERNA
PRESSURE TRANSMITTER
SENSORE DI PRESSIONE
12
C
For signals 0/4...20mA with two-wire
sensor
• Comply with polarity
C = Sensor output
A = Sensor power supply
4...20mA
9
A
PRESSURE TRANSMITTER
SENSORE DI PRESSIONE
Serial input
-
RS485 Modbus RTU communication
6
RS485
+
7
11
Shield/Schermo
Do not use LT (line termination)
resistors
• For networks with more than five
instruments supply in low voltage
12 ATR 142 - User manual
Relay Q1 Output
7
Q2
6
Capacity:
Q1: 8A, 250Vac,resistive loads,105 operations. 30/3A, 250Vac, cosφ=0.3, 105
operations.
Q2: 5A, 250Vac, resistive loads, 105
operations.
20/2A, 250Vac, cosφ=0.3, 105 operations.
5
4
Q1
3
SSR output
8
SSR command output 12V/30mA
SSR
9
Digital Input
10
11
Digital input according to parameter 
The use of digital input in this version is
possible only with TC sensors or 0…10V,
0/4…20mA and 0…40mV signals
User manual - ATR 142 13
5
Configuration EASYUP
To simplify the setting of parameters and the integration of
the different components involved in the control system,
Pixsys introduces the EASY-UP coding which allows to set
sensors and/or command outputs in one single step.
By means of the code listed in the data sheet enclosed to the
sensor or actuator (SSR, motorized valve etc..) the EASY-UP
coding will set the relevant main parameters on the controllers (ex. selection of PT100 on parameter “Sensor” and the
corresponding measuring range on parameters “Lower and
Upper limits of setpoint”)
Different codes may be entered on the controllers in sequence to configure inputs, control output or retransmission of
signal.
14 ATR 142 - User manual
6
Display and Keys Functions
1
ATR 142
9
12
1 2 3
M T R
10
3
6.1
4
5
6
11
7
8
2
Numeric Indicators (Display)
Normally displays the process. During the
1
2
6.2
 configuration phase, it displays the parameter
being inserted.
Normally displays the setpoint. During the
 configuration phase, it displays the parameter
value being inserted.
Meaning of Status Lights (Led)
2
ON when the output command is on. For
motorised valve command, led is ON when valve is
opening and blinks when closing.
ON when alarm 1 is on.
5
3
ON when alarm 2 is on.
6
M
7
T
8
R
ON when the “Manual” function is on.
ON when the controller is running an “Autotuning”
cycle.
ON when the controller communicates via serial
port.
3
1
4
User manual - ATR 142 15
6.3
Keys
9
10
11
SET
12
FN C
7
7.1
• Allows to decrease main setpoint.
• During configuration phase, allows to slide
through parameters. Together with SET key it
modifies them.
• Pressed after SET key it allows to decrease
alarm setpoint.
• Allows to increase main setpoint.
• During configuration phase, allows to slide
through parameters. Together with SET key it
modifies them.
• Pressed after SET key it allows to increase alarm
setpoint.
• Allows to display alarm setpoint and runs the
autotuning function.
• Allows to modify configuration parameters.
• Allows to run the autotuning function and to
select Manual/automatic operation.
• Allows to enter/exit for configurator procedure.
Controller Functions
Modifying Main Setpoint and Alarm
Setpoint Values
Setpoint value can be changed by keyboard as follows:
Press
Effect
Do
Value on display 2
Increase or decrease
9
or
changes
main setpoint
Visualize alarm
10
SET
setpoint on display 1
Increase or decrease
Value on display 2
the alarm set point
11
or
changes
value
16 ATR 142 - User manual
7.2
Auto-Tune
Tuning procedure calculates the controller parameters and
can be manual or automatic according to selection on parameter 46 .
7.3
Manual Tuning
Manual procedure allows the user greater flexibility to decide
when to update PID algorithm work parameters. The procedure can be activated in two ways.
• Running Tuning by keyboard:
Press FNC key until display 1 shows the writing  with
display 2 showing , press
, display 2 shows . The
T led switches on and the procedure begins.
• Running Tuning by digital input:
Select  on parameter 50 
At first activation of digital input (commutation on front panel)
T led switches ON and at second activation switches off.
User manual - ATR 142 17
7.4
Automatic Tuning
Automatic tuning activates whenever the controller is switched
on or when the setpoint is modified to a value over 35%.
To avoid an overshoot, the treshold where the controller calculates new PID parameters is determined by the setpoint value
minus the “Set Deviation Tune” (see Parameter 47 ).
To exit Tuning and keep PID values unchanged, just press the
FNC key until display 1 shows the writing  with the display
showing , press
, display 2 shows .
The T led switches off and the procedure finishes.
7.5
Soft Start
To reach the setpoint the controller can follow a gradient
expressed in units (e.g. degree/hour).
Enter this gradient on parameter 51  with the chosen
units/hour; only on subsequent activation the controller
uses soft start function.
Automatic/manual tuning cannot be enabled if the Soft start
is active.
7.6
Automatic/Manual Regulation for %
Output Control
This function allows to select automatic functioning or manual command of the output percentage.
Parameter 49 , can select two methods.
• First selection 
pressing the FNC key display 1 shows , while display 2
shows .
18 ATR 142 - User manual
Press the
key to select  mode; it is now possible, to
change the output percentage using the keys
and
. To return to automatic mode, using the same procedure,
select  on display 2: M led switches off and functioning returns to automatic mode.
• Second selection 
same functioning, but with two important variants:
• If there is a temporary power failure or after switch-off,
manual functioning as well as the previous output
percentage value will be maintained at restarting.
• If the sensor breaks during automatic functioning, controller moves to manual mode while maintaining the
output percentage command unchanged as generated
by the PID immediately before breakage.
7.7
Pre-Programmed Cycle
Pre-programmed cycle function activates by setting  on
parameter 48 
Controller reaches setpoint1 basing on the gradient set on parameter 51 , then it reaches max. power up to setpoint2.
When the process reaches max. power, this setpoint is maintained for the time set on parameter 52 
At expiry, process will reach ambient temperature according
to gradient entered on parameter 64 , then command
output will be disabled and display will visualize .
User manual - ATR 142 19
Setpoint
Setpoint 2
Maintenance time
Mantenimento
Max Power
Max Potenza
Cooling
Raffreddamento
Setpoint 1
Rising gradient
Gradiente di salita
Time
Cycle starts at each activation of the controller, or via digital
input if it is enabled for this type of functioning (see parameter 50 ).
7.8
Memory Card (optional)
Parameters and setpoint values can be duplicated from one
controller to another using the Memory card.
There are two methods:
• With the controller connected to the power supply
Insert the memory card when the controller is off.
On activation display 1 shows  and display 2 show
 (Only if the correct values are saved in the memory
card). By pressing the
key display 2 shows , then
confirm using the FNC key. The controller loads the new
data and starts again.
20 ATR 142 - User manual
• With the controller not connected
to power supply.
The memory card is equipped with
an internal battery with an autonomy of about 1000 uses.
Insert the memory card and press
the programming button .
When writing the parameters, the led turns red and on
completing the procedure it changes to green. It is possible
to repeat the procedure without any particular attention.
Updating Memory Card
To update the memory card values, follow the procedure
described in the first method, setting display 2 to  so as
not to load the parameters on controller1.
Enter configuration level and change at least one parameter.
Exit configuration. Changes are saved automatically.
7.9
Loading default values
This procedure allows to restore factory settings of the
instrument.
Press
Effect
Do
Display 1 shows 
C
with the 1st digit
FN
1
for 3 sec. flashing, while display
2 shows 
1
If on activation the controller does not display  it means no data
have been saved on the memory card, but it is possible to update values.
User manual - ATR 142 21
2
3
or
Change the flashing
digit and move to the
Enter password 
next one using the
SET key.
Instrument loads
SET
to confirm default settings
Turn off and restart
the instrument
7.10 LATCH ON Functions
For use with input  (potentiometer 6KΩ) and  (potentiometer 150KΩ) and with linear input (0…10V, 0...40mV,
0/4…20mA), it is possible to associate start value of the scale
(parameter 6 ) to the minimum position of the sensor
and value of the scale end (parameter 7 ) to the maximum position of the sensor (parameter 8  configured as
).
It is also possible to fix the point in which the controller will
display 0 (however keeping the scale range between 
and ) using the “virtual zero” option by setting 
or  in parameter 8  If you set  the virtual zero
will reset after each activation of the tool; if you set  the
virtual zero remains fixed once tuned.
To use the LATCH ON function, configure according to required operation the parameter 2
2
The tuning procedure starts by exiting the configuration after changing
the parameter.
22 ATR 142 - User manual
For the calibration procedure refer to the following table:
Press
Effect
Do
Place the sensor on the
Exit parameters
minimum functioning
1
FNC configuration. Display 2
value (associated with
shows the writing 
)
Place the sensor on the
Set the value to
maximum functioning
2
minimum.
position
The display shows 
(associated with )
To exit standard
procedure press FNC .
Set the value to
3
maximum.
For “virtual zero”
The display shows  settings place the sensor
on zero point.
Set the virtual zero
value. The display shows
 NB: for selection
To exit the procedure
4 SET of  the procedure
press FNC .
on point 4 should
be followed at each
re-activation.
Min
Max
Zero
User manual - ATR 142 23
7.11 Digital Input Functions
Digital input is programmable for several functions which
are useful to simplify controller operability. Select the chosen
function on parameter 50 
• Hold function (enabled by setting  or ) allows
to lock the reading of sensors when the digital input is active (useful for wide ranging oscillation on less significant
values). During the hold phase, display 2 flashes and shows
.
• Enables/disables the autotuning function by digital input
if the parameter  is set on 
• Enable regulation with  or 
• Switch from automatic to manual functioning if  is
set on  or 
• Start of pre-programmed cycle (see par. 7.7) with 
• Change setpoint function.
This function is useful where there are 2 to 4 working thres
holds required during system functioning without having
to press the arrow keys.
To enable the function use the parameter , by
selecting the number of setpoints desired (no. thresholds
switch). They can be switched during functioning by
pressing the SET key.
24 ATR 142 - User manual
NB: digital input functions are not available with sensors
PT100, NI100, NTC, PTC, PT500, PT1000 and potentiometers.
7.12 Dual Action Heating-Cooling
ATR142 is suitable also for systems requiring a combined
heating-cooling action.
(  =  and with a  greater than 0), and one of the
alarms ( or ) must be configured as  Command
output must be connected to the actuator responsible for
heat, while the alarm will control cooling action.
Parameters to configure for the Heating PID are:
 =  Command output type (Heating)
 : Heating proportional band
 : Integral time of heating and cooling
 : Derivative time of heating and cooling
 : Heating time cycle
The parameters to configure for the Cooling PID are the
following (example: action associated to alarm1):
 =  Alarm1 selection (cooling)
 : Proportional band multiplier
 : Overlapping/Dead band
 : Cooling time cycle
Parameter  (that ranges from 1.00 to 5.00) determines
the proportional band of cooling basing on the formula:
Cooling proportional band =  * 
This gives a proportional band for cooling which will be the
same as heating band if  = 1.00, or 5 times greater if
 = 5.00. The integral time and derivative time are the
same for both actions.
User manual - ATR 142 25
Parameter  determines the percentage overlapping
between the two actions. For systems in which the heating
and cooling output must never be simultaneously active a
dead band (  ≤ 0) can be configured, and viceversa an
overlapping (  > 0).
The following figure shows an example of dual action PID
(heating-cooling) with  = 0 and  = 0.
 x  (COOL)
 < 0
SPV
PV
 (HEAT)
ATTIVO
ACTIVE
ATTIVO
ACTIVE
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
 x  (COOL)
 = 0
SPV
 (HEAT)
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
26 ATR 142 - User manual
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
 x  (COOL)
 > 0
SPV
 (HEAT)
PV
ATTIVO
ACTIVE
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
ATTIVO
ACTIVE
Parameter  has the same meaning of the cycle time 
for heating.
Parameter  (cooling fluid) pre-selects the proportional
band multiplier  and the cooling PID cycle time 
basing on the type of cooling fluid:



Cooling fluid type
Air
1.00
10



8
Oil
1.25
4
Water
2.50
2
Timer operation
Timer operation is enabled by parameter 63  To modify
duration of counting time, follow the steps below:
Press
Effect
Do
Press until  or
1
 visualized on
SET
display 1.
Increase or decrease
Digits on display 2
time value for the
2
or
changes.
selected timer.
Below a description of available options for Timer operation.
User manual - ATR 142 27
8.1
Single Timer
This option enables one single Timer and the time is selectable by the operator.
To achieve this operation set parameter 63  as follows:
•  (Single Timer Seconds) time-basis in seconds (mm.ss)
•  (Single Timer Minutes) time-basis in minutes (hh.mm)
To start/stop the Timer, press FNC for 1 “.
During the counting, Led R is On and display2 shows decrementing time. At elapsing of Timer, led R switches off and
display 2 flashes, visualising the programmed time until any
key is pressed.
Start/Stop of Timer is possibile also by digital input, selecting
 on parameter 50 
8.2
Dual Timer
This option enables two Timers and the time is selectable by
the operator: timers cannot be started at same time.
To achieve this operation set parameter 63 as follows:
•  (Double Timer Seconds) time-basis in seconds (mm.ss)
•  (Double Timer Minutes) time-basis in minutes (hh.mm)
Check the table below for the Start procedure:
Press
Effect
Do
Press until  or 
1
FN C
 visualized on display 1.
Start the Timer. Display 2
Back to point 1, after
shows decrementing time
selection of running Timer
and Led R switches on
2
to stop counting.
press
(fixed for timer 1, flashing
Led R switches off.
for timer 2).
At elapsing of Timer the led R switches off and display
28 ATR 142 - User manual
2 flashes, showing the programmed time until any key is
pressed. Start/Stop of Timer by digital input is NOT available
for Dual Timer mode.
8.3
Dual Sequential Timer
This option enables two Timers and the time is selectable by
the operator. At elapsing of Timer 1, counting of Timer 2 will
automatically start . At elapsing of Timer 2, counting will stop.
To achieve operation of dual sequential Timer set the parameter 63  as follows:
•  (Double Sequential Timer Seconds) time-basis in
seconds (mm.ss)
•  (Double Sequential Timer Minutes) time-basis in
minutes (hh.mm)
To start/stop the Timer, press key FNC for 1“. During the counting,
Led R is On (fixed for Timer 1, flashing for Timer 2) and display2
shows decrementing time. Start is always made on Timer 1. At
elapsing of Timer, led R is switched off and display 2 shows
setpoint value. Start/Stop of Timer is possibile also by digital
input, selecting  on parameter 50 
8.4
Dual Timer Loop
This option enables 2 Timers and the time value is selectable
by the operator. At elapsing of one Timer, the other one will
automatically start and this sequence is repeated cycling.
To achieve operation of dual timer loop set the parameter 63
 as follows:
•  (Double Timer Loop Seconds) time-basis in seconds
(mm.ss)
User manual - ATR 142 29
•  (Double Timer Loop Minutes) time-basis in minutes
(hh.mm)
To start/stop the Timer, press FNC for 1 “.
During the counting, Led R is On (fixed for Timer1, flashing
for Timer 2) and display2 shows decrementing time. Start is
always made on Timer 1.
Start/Stop of Timer is possibile also by digital input, selecting
 on parameter 50 
8.5
Relating Timers to Alarms
It is possible to associate the alarms (relay or SSR outputs) to
the timers by parameters 23  and 31  The table below is showing the combined operation of alarms and Timers.
Selection
Description
par. 23 or 31
Alarm active as long as Timer 1 is in

Timer 1 Start Alarm Start mode (Timer active)
Alarm active at elapsing of Timer1 until
any key is pressed. Option not available

Timer 1 End Alarm for Dual sequential Timer and Dual
Timer Loop.

Timer 1 Warning
Expiring
Alarm active for the last 5” of Timer1
Alarm active as long as Timer 2 is in

Timer 2 Start Alarm Start mode (Timer active)
Alarm active at elapsing of Timer2 until
any key is pressed. Option not available

Timer 2 End Alarm for Dual sequential Timer and Dual
Timer Loop.
30 ATR 142 - User manual

Timer 2 Warning
Expiring
Alarm active for the last 5” of Timer2
Alarm active as long as Timers 1 and 2

Timer 1-2 Start Alarm are in Start mode (Timers active)
Alarm active at elapsing of Timers 1 and
2 until any key is pressed. Option not

Timer 1-2 End Alarm available for Dual sequential Timer and
Dual Timer Loop.

Alarm active for the last 5” of Timers 1
Timer 1-2 Warning
and 2.
expiring
9
9.1
Serial Communication
Slave
ATR142-ABC-T is equipped with RS485, it can receive and
broadcast data via serial communication using MODBUS RTU
protocol. The device operates as slave if parameter 59  is
set as . This function enables the control of multiple devices
connected to a supervisory system (SCADA).
Each controller will answer to a master query only if the query
contains same address as on parameter  The permitted
addresses range from 1 to 254 and there should not be controllers with the same address on the same line.
Address 255 can be used by the master to communicate with all
the connected equipment (broadcast mode), while with 0 all
the devices receive the command, but no answer is expected.
ATR142 can introduce an answer delay (in milliseconds) to master request. This delay has to be set on parameter 58 
User manual - ATR 142 31
At each parameter configuration, instrument storeschange
values in the EEPROM memory (100000 writing cycles), while
setpoints are stored with a delay of 10 seconds after last
modification. NB: modifications made to words different from
those described in the following table can lead to instrument
malfunction.
Modbus RTU protocol features
Modbus RTU protocol features
Selectable on parameter 56
 4800bit/sec
 9600bit/sec
Baud-rate
 19200bit/sec
 28800bit/sec
 38400bit/sec
 57600bit/sec
Format
8, N, 1 (8bit, no parity, 1 stop)
Supported
functions
WORD READING (max 20 word) (0x03, 0x04)
SINGLE WORD WRITING (0x06)
MULTIPLE WORDS WRITING (max 20 word)
(0x10)
The list below includes all available addresses:
RO = Read Only
R/W = Read/Write
Modbus address
Modbus
Description
address
0
Device type
1
Software version
5
Slave Address
32 ATR 142 - User manual
WO = Write Only
Read Reset
Write value
RO EEPROM
RO EEPROM
R/W EEPROM
6
50
51
500
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
Boot version
Automatic addressing
System code comparison
Loading default values:
9999 restore all values
9998 restore all values except for
baud-rate and slave address
9997 restore all values except for
slave address
9996 restore all values except for
baud-rate
Process (with tenths of degree for
temperature sensors; digits for
linear sensors)
Setpoint1
Setpoint2
Setpoint3
Setpoint4
Alarm1
Alarm2
Setpoint gradient
Outputs status (0=off, 1=on)
Bit 0 = Q1 relay
Bit 1 = Q2 relay
Bit 2 = SSR
Heating output percentage
(0-10000)
Cooling output percentage
(0-10000)
Alarms status (0=none, 1=active)
Bit0 = Alarm 1
Bit1 = Alarm 2
RO EEPROM
WO
WO
-
WO
0
RO
-
R/W
R/W
R/W
R/W
R/W
R/W
RO
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
RO
0
RO
0
RO
0
RO
0
User manual - ATR 142 33
1012
1013
1014
1015
1016
1017
1018
1019
1100
Manual reset:
write 0 to reset all the alarms.
In reading
(0=not resettable, 1=resettable):
Bit0 = Alarm 1
Bit1 = Alarm 2
Error flags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold junction error
Bit3 = Process error (sensor)
Bit4 = Generic error
Bit5 = Hardware error
Bit6 = Master off-line
Bit7 = Missing calibration data
Cold junction temperature
(tenths of degree)
Start/Stop
0=controller in STOP
1=controller in START
Lock conversion ON/OFF
0=Lock conversion off
1=Lock conversion on
Tuning ON/OFF
0=Tuning off
1=Tuning on
Automatic/manual selection
0=automatic
1=manual
OFF LINE* time (milliseconds)
Process visualized (decimal as
display)
34 ATR 142 - User manual
WO
0
RO
0
RO
-
R/W
0
R/W
0
R/W
0
R/W
0
R/W
0
RO
-
1101
1102
1103
1104
1105
1106
1107
1108
1109
1110
1111
2001
...
2064
3000
3001
*
**
Visualized Setpoint 1 (decimal as
display)
Visualized Setpoint 2 (decimal as
display)
Visualized Setpoint 3 (decimal as
display)
Visualized Setpoint 4 (decimal as
display)
Visualized Alarm 1 (decimal as
display)
Visualized Alarm 2 (decimal as
display)
Setpoint gradient (decimal as
display)
Heating output percentage
(0-1000)
Heating output percentage (0-100)
Cooling output percentage
(0-1000)
Cooling output percentage (0-100)
Parameter 1
...
Parameter 64
Disabling serial control of
machine**
First word display1 (ASCII)
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
RO
EEPROM
RO
0
RO
0
RO
0
RO
0
R/W EEPROM
...
...
R/W EEPROM
WO
0
R/W
0
If value is 0, the control is disabled. If different from 0, it is the max. time
which can elapse between two pollings before the controller goes offline. If it goes off-line, the controller returns to Stop mode, the control
output is disabled but the alarms are active.
By writing 1 on this word, the effects of the writing are cancelled on all
the Modbus addresses from 3001 to 3022. Control therefore returns to
the controller.
User manual - ATR 142 35
...
3008
3009
...
3016
3017
3018
3019
3020
3021
9.2
…..
Eighth word display1 (ASCII)
First word display2 (ASCII)
…..
Eighth word display2 (ASCII)
Word LED
Bit 0 = LED 1
Bit 1 = LED 2
Bit 2 = LED 3
Bit 3 = LED MAN
Bit 4 = LED TUN
Bit 5 = LED REM
Word keys
(write 1 to command keys)
Bit 0 =
Bit 1 =
Bit 2 = SET
Bit 3 = FNC
Word serial outputs
Bit 0 = Q1 relay
Bit 1 = Q2 relay
Bit 2 = SSR
Word serial outputs state if off-line
Bit 0 = Q1 relay
Bit 1 = Q2 relay
Bit 2 = SSR
Word serial process
R/W
R/W
R/W
R/W
R/W
0
0
0
0
0
R/W
0
R/W
0
R/W
0
R/W
0
R/W
0
Master
The device works as master if value selected on parameter 59
 is other than .
36 ATR 142 - User manual
9.2.1 Master Mode in retransmission
Selecting this mode, the device will write the value to be
retransmitted to the address selected on parameter 60 
on the slave devices having same ID as value selected on
parameter 57 .
Regarding retransmission of setpoint values, after writing
the value on slaves, ATR142 starts reading the corresponding
word, so that any modification of value on the slave will be
automatically updated also on the Master. Two successive
pollings will be delayed for the time selected on parameter
57 .
The following table includes the options allowing the Master
mode in retransmission and the relevant retransmitted value.

Description

Write Process
Write process value

Write and read command setpoint value
Read/Write
Command Setpoint

Write Output
Percentage

Read/Write Alarm 1
Write output percentage rated by P.I.D.
function (Range 0-10000)
Write and read alarm 1 setpoint value
User manual - ATR 142 37
The read/written value might be rescaled according to the
proportion described in the following table:
Value limits input Limits of rescaled value

Min
Max
Min
Max

Write
Process

Read/Write
Command
Setpoint

Write
Output
Percentage

Read/Write
Alarm 1






Lower Limit Upper Limit
Lower
Upper
Retransmis- RetransmisLimit Input Limit Input
sion
sion

Lower
Limit
Setpoint

0
10000


Lower
Limit
Setpoint

Upper Lower Limit Upper Limit
Limit
Retransmis- RetransmisSetpoint
sion
sion

Lower Limit Upper Limit
Retransmis- Retransmission
sion


Upper Lower Limit Upper Limit
Limit
Retransmis- RetransmisSetpoint
sion
sion
The input value (included between minimum and max limit) is linearly converted into the retransmitted value which is included
between min and max output value. Rescaling is not executed if
parameters  and  have the same value.
38 ATR 142 - User manual
9.2.2 Master Mode Remote process
To enable this function it is necessary to select  on parameter 59 . In this mode the process value on ATR142 is a
value read via serial communication. The ID of the slave must
be same as value selected on parameter 57  and the
word to read is selected on parameter 60 . Two successive pollings will be delayed for the time selected on parameter
57  The read value might be rescaled according to the
proportion described in the following table:
Limits of read value Limits of rescaled value

Min
Max
Min
Max


Read
Process

Lower
Upper


Limit Re- Limit Re- Lower Limit Upper Limit
Input
Input
transmis- transmission
sion
10 Configuration
10.1 Modify Configuration Parameter
For configuration parameters see paragraph 11.
Press
Effect
Do
Display 1 shows 
C
with the 1st digit
FN
1
for 3 sec. flashing, while display
2 shows .
Change the flashing
digit and move to the
2
Enter password 
or
next one using the
SET key.
User manual - ATR 142 39
3
4
Display 1 shows the
first parameter and
to confirm display 2 shows the
value.
Slide up/down
or
through parameters
SET
SET
5
+
or
6
11
FN C
Increase or decrease
the value displayed
by pressing firstly SET
and then an arrow
key.
Enter the new data
which will be saved
on releasing the keys.
To change another
parameter return to
point 4.
End of configuration
parameter change.
The controller exits
from programming.
Table of Configuration Parameters
The following table includes all parameters. Some of them
will not be visible on the models which are not provided with
relevant hardware features.
1
 Command Output
select command output type.


> Default (Factory setting)


40 ATR 142 - User manual
ATR142-ABC
Command
Q2
Q1




Q1(opens) Q2(closes)



ATR142-ABC-T
Command
Q1
SSR
Q1(opens) SSR(closes)

Alarm 1
Q1
Q2
Q1
SSR
Alarm 2
SSR
SSR
Q2
-
Alarm 1
SSR
Q1
-
2  Sensor
analogue input configuration.
 Tc-K -260…1360°C > Default
 Tc-S -40…1760°C
 Tc-R -40…1760°C
 Tc-J -200…1200°C

PT100 -200…600°C
 PT100 -200…140°C

NI100 -60…180°C

NTC10K -40…125°C

PTC1K -50…150°C

PT500 -100…600°C
 PT1000 -100…600°C

0…10Volt

0…20mA

4…20mA

0…40mVolt
 Potenz.Max 6KΩ F.S.
 Potenz.Max 150KΩ F.S.
User manual - ATR 142 41
3 
Decimal Point
select number of displayed decimal points.

> Default



4  Lower Limit Setpoint
lower limit setpoint.
-999…+9999 [digit3] (degrees.tenths for temperature
sensors) Default: 0.
5  Upper Limit Setpoint
upper limit setpoint.
-999…+9999 [digit3] (degrees.tenths for temperature
sensors) Default: 1750.
6  Lower Linear Input
lower range limit AN1 only for linear input.
-999…+9999 [digit3] Default: 0.
7  Upper Linear Input
upper range limit AN1 only for linear input.
-999…+9999 [digit3] Default: 1000.
8  Latch On Function
automatic setting of limits for Linear input.

Disabled > Default
 Standard
 Virtual Zero Stored
  Virtual Zero Initialized
42 ATR 142 - User manual
9  Offset Calibration
number added to process value visualized on display
(usually correcting the ambient temperature value).
-999…+1000 [digit3] for linear sensors and potentiometers.
-99.9…+100.0 (degrees.tenths for temperature sensors). >
Default: 0.0.
10  Gain Calibration
this % is multiplied with displayed value to calibrate the
process value. -99.9%…+100.0% > Default: 0.0
11  Action type
regulation type
 Heating (N.A.) > Default
 Cooling (N.C.)
 If process is above setpoint, output is disabled
(Heating).
12  Command Reset
type of reset for state of command contact (always
automatic in PID functioning).
 Automatic Reset > Default
 Manual Reset
 Manual Reset Stored
13  Command State Error
state of contact for command output in case of error.

> Default

14  Command Led
state of OUT1 led corresponding to the relevant contact.


> Default
User manual - ATR 142 43
15  Command Hysteresis
hysteresis in ON/OFF or dead band in P.I.D.
-999…+999 [digit3], (degrees.tenths for temperature
sensors) > Default: 0.0
16  Command Delay
(only in ON/OFF functioning).(In case of servo valve it also
functions in PID and represents the delay between the
opening and closure of the two contacts).
-180…+180 seconds, tenths of second in case of servo valve.
Negative: delay in switching off phase.
Positive: delay in activation phase.
Default: 0.
17  Command Setpoint Protection
allow/deny modifications of command setpoint by frontal
keyboard.
 > Default
 Locked
18 
Proportional Band
process inertia in units (°C if temperature).
0 on/off if  equal to 0. > Default
1-9999 [digit3], (degrees for temperature sensors).
19 
Integral Time
process inertia in seconds
0.0-999.9 sec. (0 excludes integral) > Default: 0.
20 
Derivative Time
normally ¼ of integral time.
0.0-999.9 sec. (0 excludes derivative) > Default: 0.
The display of decimal point depends on the setting of parameter 
and the parameter 
44 ATR 142 - User manual
3
21 
Cycle Time
Cycle time for time-proportioning output (10/15sec for
PID contactors, 1 sec for PID on SSR or value declared by
manufacturer for motorised valves)
0.1-300.0 sec. > Default: 10.0.
For motorised valve min. time is 1.0 sec
22  Output Power Limit
limit of output power %.
10-100 % > Default: 100
23  Alarm
operating mode for Alarm 1. Intervention of the alarm is
associated to AL1.

Disabled > Default
 Absolute Alarm (see par. 12)
 Band Alarm (see par. 12)
 High Deviation Alarm (see par. 12)
 Low Deviation Alarm (see par. 12)
 Absolute Command setpoint Alarm
 Start Alarm, Active in Run
 Cooling
 Timer 1 Start Alarm
 Timer 1 End Alarm
 Timer 1 Warning Expiring
 Timer 2 Start Alarm
 Timer 2 End Alarm
 Timer 2 Warning Expiring
 Timer 1-2 Start Alarm
 Timer 1-2 End Alarm
 Timer 1-2 Warning Expiring
User manual - ATR 142 45
24  Alarm 1 State Output
alarm 1 output contact and intervention type
 (n.o. start) Normally open, active at start > Default
 (n.c. start) Normally closed, active at start.
 (n.o. threshold) Normally open,active on reaching
alarm4.
 (n.c. threshold) Normally closed on reaching alarm4.
25  Alarm 1 Reset
type of Reset for contact of alarm 1.
 Automatic Reset > Default
 Manual Reset
 Manual Reset Stored
26  Alarm 1 State Error
state of contact for alarm 1 output in case of error.

> Default

27  Alarm 1 Led
state of OUT2 led corresponding to the relative contact.


> Default
28  Alarm 1 Hysteresis
-999…+999 [digit5], (degrees.tenths for temperature sensors).
29  Alarm 1 Delay
-180…+180 Sec. > Default: 0.
Negative: delay at exit from alarm
Positive: delay at starting of alarm
4
5
On activation the output is inhibited if the controller is in alarm mode.
Activates only if alarm condition reappers after that it was restored.
The display of decimal point depends on the setting of parameter 
and the parameter 
46 ATR 142 - User manual
30  Alarm 1 Setpoint Protection
does not allow the user to modify setpoint.
 > Default
 Locked
 Locked and hidden
31  Alarm 2
Alarm 2 selection. Alarm intervention is associated to AL2.

Disabled > Default
 Absolute Alarm
 Band Alarm
 High Deviation Alarm
 Low Deviation Alarm
 Absolute Command setpoint Alarm
 Start Alarm, Attivo in Run
 Cooling
 Timer 1 Start Alarm
 Timer 1 End Alarm
 Timer 1 Warning Expiring
 Timer 2 Start Alarm
 Timer 2 End Alarm
 Timer 2 Warning Expiring
 Timer 1-2 Start Alarm
 Timer 1-2 End Alarm
 Timer 1-2 Warning Expiring
32  Alarm 2 State Output
alarm 2 output contact and intervention type.
 (n.o. start) Normally open, active at start. > Default
 (n.c. start) Normally closed, active at start.
 (n.o. threshold) Normally open, active on reaching alarm6
 (n.c. threshold) Normally closed, active on reaching alarm6
6
On activation the output is inhibited if the controller is in alarm mode.
Activates only if alarm condition reappers, after that it was restored.
User manual - ATR 142 47
33  Alarm 2 Reset
type of Reset for contact of alarm 2.
 Automatic Reset > Default
 Manual Reset
 Manual Reset Stored
34  Alarm 2 State Error
state of contact for alarm 2 output in case of error.

> Default

35  Alarm 2 Led
state of OUT2 led corresponding to relative contact.


> Default
36  Alarm 2 Hysteresis
-999…+999 [digit7], (degrees.tenths for temperature
sensors). > Default: 0.
37  Alarm 2 Delay
-180…+180 Sec. > Default: 0.
Negative: delay in alarm output phase.
Positive: delay in alarm entry phase.
38  Alarm 2 Setpoint Protection
Alarm 2 set protection.
Does not allow operator to change setpoint value.
 > Default
 Locked
 Locked and hidden
39  Cooling Fluid
select type of cooling fluid for Heating/Cooling PID
48 ATR 142 - User manual



Air > Default
Oil
Water
40  Proportional Band Multiplier
1.00-5.00 > Default: 1.00.
41 . Overlap/Dead Band
overlapping/Dead band
-20.0-50.0% > Default: 0.
42  Cooling Cycle Time
cycle time for cooling output.
1-300 sec. > Default: 10.
43  Conversion Filter
ADC filter,
number of means on analogue-digital
conversions.

Disabled
 2 Samples Mean
 3 Samples Mean
 4 Samples Mean
 5 Samples Mean
 6 Samples Mean
 7 Samples Mean
 8 Samples Mean
 9 Samples Mean
 10 Samples Mean > Default
 11 Samples Mean
 12 Samples Mean
 13 Samples Mean
 14 Samples Mean
 15 Samples Mean
User manual - ATR 142 49
44  Conversion Frequency
Frequency of sampling for analogue-digital converter.
 242 Hz Max ADC conversion frequency
 123 Hz
 62 Hz
 50 Hz
 39 Hz
 33.2 Hz
 19.6 Hz
 16.7 Hz > Default
 12.5 Hz
 10 Hz
 8.33 Hz
 6.25 Hz
 4.17 Hz Min. ADC conversion frequency
45  Visualization Filter
slow down the refresh of display in order to simplify
the reading (keeping unchanged the ADC conversion
frequency)

Disabled
 Pitchfork filter > Default
 First Order
 First Order with Pitchfork
 2 Samples Mean
 3 Samples Mean
 4 Samples Mean
 5 Samples Mean
 6 Samples Mean
 7 Samples Mean
 8 Samples Mean
 9 Samples Mean
 10 Samples Mean
50 ATR 142 - User manual
46  Tune
tuning type selection

Disabled > Default
 Automatic. PID parameters are calculated at each
activation and/or change of setpoint.
 Manual. Launch by keyboard or by digital input.
47  Setpoint Deviation Tune
select the deviation from the command setpoint as
threshold used by Autotuning to calculate PID parameters.
0-5000 [digit7], (degrees.tenths for temperature sensors) >
Default: 10.
48  Operatine Mode
select operating mode
 Controller > Default
 Programmed Cycle
 2 Thresholds Switch
 2 Thresholds Switch Impulsive
 3 Thresholds Switch Impulsive
 4 Thresholds Switch Impulsive
49  Automatic/Manual
enable automatic/manual selection.

Disabled > Default

Enabled
 Enabled Stored
50  Digital Input
Digital input functioning.
Par. 48 selection must be  or 

Disabled > Default
 Start/Stop
 Run n.o.
User manual - ATR 142 51
 Run n.c.
 Lock Conversion n.o. (Lock visualisation on display
with N.O. contact)
 Lock Conversion n.c. (Lock visualisation on display
with N.C. contact)
 Tune > Manual
 Automatic Manual impulse
 Automatic Manual Contact
 Timer 1 Start Stop
51  Gradient
Rising gradient for soft start or pre-programmed cycle
0 Disabled > Default: 0.
1-9999 Digit/time7 (degrees/hours with display of tenths if
temperature)
52  Maintenance Time
maintenance time for pre-programmed cycle
00.00-24.00 hh.mm > Default: 00.00
53  User Menu Cycle Programmed
Allows the rising/falling gradient and the maintenance time
to be changed from the user menu in pre-programmed
cycle functioning.

Disabled > Default
 Rising Gradient (modify gradient)
 Maintenance Time (modify time)
 Rising Gradient and Maintenance Time (modify both)
 Falling Gradient (modify cooling gradient)
 Rising and Falling Gradient (modify rising and
cooling gradient)
 Falling Gradient and Maintenance Time
The display of decimal point depends on the setting of parameter 
and the parameter 
52 ATR 142 - User manual
7

All (modify all parameters for pre-programmed cyle)
54  Visualization Type
select visualization for display 1 and 2
 1 Process, 2 Setpoint > Default
 1 Process, 2 Hide after 3 sec.
 1 Setpoint, 2 Process.
 1 Setpoint, 2 Hide after 3 sec.
55  Degree
select degree type

Celsius > Default

Fahrenheit
56  Baud Rate
select baud rate for serial communication






> Default
57  Slave Address
select slave address for serial communication
0 – 255 > Default: 254.
58  Serial Delay
select serial delay
0 – 100 milliseconds > Default: 20.
User manual - ATR 142 53
59  Master
select master mode.

Disable > Default
 Write Process
 Read Write Command Setpoint
 Write Output Percentage
 Read Write Alarm 1 Setpoint
 Read Process
60  Address Retransmission
select address for retransmission.
0x0000 – 0xFFFF hexadecimal > Default: 0x03E9.
61  Lower Limit Retransmission
lower limit retransmission range.
-999 - 9999 [digit8], (degrees for temperature sensors) >
Default: 0.
62  Upper Limit Retransmission
upper limit retransmission range.
-999 – 9999 [digit9], (degrees for temperature sensors) >
Default: 0.
63  Timer Function
enable 1 or 2 Timers which may be set from user menu and
which can be related to alarms.

Disable > Default
 Single Timer Seconds
 Double Timer Seconds
 Double Sequential Timer Seconds
8
9
The display of decimal point depends on the setting of parameter 
and the parameter 
If parameter 61  and 62  have the same value, retransmitted
value is not rescaled.
54 ATR 142 - User manual





Double Timer Loop Seconds
Single Timer Minutes
Double Timer Minutes
Double Sequential Timer Minutes
Double Timer Loop Minutes
64  Falling Gradient
cooling gradient for pre-programmed cycle
0 desabled (uncontrolled cooling) > Default: 0.
1-9999 degrees/hour, with display of tenths
12
Alarm Intervention Modes
Absolute Alarm or Threshold Alarm ( selection)
Pv.
Absolute alarm with conAlarm Spv
troller in heating functioHysteresis
ning (Par.11  selected
parameter
$+< > 0
) and hysteresis value
greater than “0” (Par.28
Time
 > 0).
On
On
Off
Off
Alarm output
NB: The example refers to alarm 1; the function can also be
enabled for alarm 2 on model that include it.
Pv
Hysteresis
parameter
$+< < 0
Absolute alarm with controller in heating functioning (Par.11  selected
) and hysteresis value
Time
less than “0” (Par.28 
On
On
Off
Off
Alarm output < 0).
NB: The example refers to alarm 1; the function can also be
enabled for alarm 2 on model that include it.
Alarm Spv.
User manual - ATR 142 55
Time
Pv
Hysteresis
parameter
$+< > 0
Alarm Spv
On
Off
On
Off
Alarm output
Time
Pv
Alarm Spv
Hysteresis
parameter
$+< < 0
On
Off
Absolute alarm with controller in cooling functioning
(Par.11  selected )
and hysteresis value greater
than “0” (Par.28  > 0).
On
Off
Absolute alarm with controller in cooling functioning (Par.11  selected
) and hysteresis value
less than “0” (Par.28  >
0).
Alarm output
NB: The example refers to alarm 1; the function can also be
enabled for alarm 2 on model that include it.
Absolute Alarm or Threshold Alarm Referring to Setpoint
Command ( selection)
Command Spv
Absolute alarm refers to the
Hysteresis
parameter
command set, with the con$+< > 0
troller in heating functioAlarm Spv
ning (Par.11  selected
) and hysteresis value
Time
greater than “0” (Par.28
On
Off
Off Alarm output
 > 0).
The command set can be changed by pressing the arrow keys
on front panel or using serial port RS485 commands.
56 ATR 142 - User manual
NB: The example refers to alarm 1; the function can also be
enabled for alarm 2 on model that include it.
Band Alarm ( selection)
Pv
Alarm Spv
Hysteresis
parameter
$+< > 0
Alarm Spv
Command Spv
Time
On
On
Off
On
Off
Off
Alarm output
Band alarm hysteresis value
greater than “0” (Par.28
 > 0).
NB: The example refers to
alarm 1; the function can
also be enabled for alarm 2
on model that include it.
Hysteresis
parameter
$+< < 0
Pv
Command Spv
Alarm Spv
Hysteresis
parameter
$+< < 0
Time
On
On
Off
On
Off
Off
Alarm output
Band alarm hysteresis value
less than “0” (Par.28 
< 0).
NB: The example refers to
alarm 1; the function can
also be enabled for alarm 2
on model that include it.
Upper Deviation Alarm ( selection)
Pv
Alarm Spv
Hysteresis
parameter
$+< > 0
Command Spv
Time
On
Off
On
Off
Upper deviation alarm value
of alarm setpoint greater
than “0” and hysteresis value greater than “0” (Par.28
 > 0).
Alarm output
User manual - ATR 142 57
NB: a) The example refers to alarm 1; the function can also be
enabled for alarm 2 on model that include it.
b) With hysteresis less than “0” (  < 0) the segmented line moves above the alarm setpoint.
Pv
Command Spv
Alarm Spv
Hysteresis
parameter
$+< > 0
Time
On
Off
On
Off
Upper deviation alarm value of alarm setpoint less
than “0” and hysteresis value greater than “0” (Par.28
 > 0).
Alarm output
NB: a) The example refers to alarm 1; the function can also be
enabled for alarm 2 on model that include it.
b) With hysteresis less than “0” (  < 0) the segmented line moves above the alarm setpoint.
Lower Deviation Alarm ( selection)
Pv
Command Spv
Hysteresis
parameter
$+< > 0
Alarm Spv
Time
On
On
Off
Off
Lower deviation alarm value
of alarm setpoint greater
than “0” and hysteresis value greater than “0” (Par.28
 > 0).
Alarm output
NB: a) The example refers to alarm 1; the function can also be
enabled for alarm 2 on model that include it .
b) With hysteresis less than “0” (  < 0) the segmented line moves under the alarm setpoint.
58 ATR 142 - User manual
Hysteresis
parameter
$+< > 0
Pv.
Alarm Spv
Command Spv
Time
On
On
Off
Off
Lower deviation alarm value
of alarm setpoint less than
“0” and hysteresis value
greater than “0” (Par. 28
 > 0).
Alarm output
NB: a) The example refers to alarm 1; function can also be
enabled for alarm 2 on model that include it.
b) With hysteresis value less than “0” (  < 0) the
dotted line moves under alarm setpoint.
13
Table of Anomaly Signals
If installation malfunctions, controller will switch off regulation output and will report the anomaly. For example, controller will report failure of a connected thermocouple visualizing
 flashing on display for other signals, see table below.
Cause
What to do
 Error in E²PROM cell
Call Assistance
 programming
Cold junction sensor
 fault or room tempera- Call Assistance
 ture outside of allowed
limits.
Incorrect configuration Check if the configu data. Possible loss of
ration parameters are
 calibration values.
correct.
Thermocouple open or Check the connection
 temperature outside of with the sensors and
 limits.
their integrity.
User manual - ATR 142 59
 Off-line in master mode
 remote process
 Missing calibration data

14
Check the serial
connection, baud-rate
and device ID.
Call Assistance
Summary of Configuration parameters
Date:
Installer:
Notes:




















Model ATR142:
System:
Command output type selection
Analog input configuration
Number of decimal points
Lower limit setpoint
Upper limit setpoint
Lower limit range An1 only for linear
Upper limit range An1 only for linear
Automatic setting of linear input limits.
Offset calibration
Gain calibration
Regulation type
Command output reset type
Contact state for command output in case
of error
Define the OUT1 led state
Hysteresis in ON/OFF or dead band in P.I.D.
Command delay
Command setpoint protection
Proportional band
Integral time
Derivative time
60 ATR 142 - User manual






























Cycle time
Limit of output power %
Alarm 1 selection
Alarm 1 output contact and intervention
type
Reset type of alarm 1 contact.
State of contact for alarm 1 output
State of OUT2 led
Alarm 1 hysteresis
Alarm1 delay
Alarm 1 set protection
Alarm 2 selection
Alarm 2 output contact and intervention
type
Reset type of alarm 2 contact
State of contact for alarm 2 output
State of OUT2 led
Alarm 2 hysteresis
Alarm 2 delay
Alarm 2 set protection
Cooling fluid type
Proportional band multiplier
Overlapping/Dead band
Cycle time for cooling output
Analog converter filter
Sampling frequency of analogue converter
Display filter
Autotuning type selection
Command setpoint deviation for tuning
threshold
Operating mode
Automatic/manual selection
Digital input functioning
User manual - ATR 142 61














Gradient for soft start
Cycle maintenance time
Gradient change and maintenance time
by user
Display data selection
Degree type selection
Select baud rate fo r serial communication
Select slave address
Select the serial delay
Select value to retransmit by ModBus
Seelct address for retransmission
Lower limit of retransmission range
Upper limit of retransmission range
Timer Function
Falling Gradiente
Notes
62 ATR 142 - User manual
User manual - ATR 142 63
Introduzione
Grazie per aver scelto un regolatore Pixsys.
Con il modello ATR142 Pixsys rende disponibile in un singolo
strumento tutte le opzioni relative alla connessione dei
sensori e al comando di attuatori, con in aggiunta un’utile
alimentazione a range esteso 24…230 Vac/Vdc. Con le 17
sonde selezionabili e l’uscita configurabile come relè o SSR
l’utilizzatore o il rivenditore può gestire al meglio le scorte
di magazzino, razionalizzando investimento e disponibilità
dei dispositivi. La serie si completa con il modello dotato di
comunicazione seriale RS485 Modbus Rtu. La ripetibilità in
serie delle operazioni di parametrizzazione è ulteriormente
semplificata dalle nuove Memory Card, dotate di batteria
interna che non richiedono cablaggio per alimentare il
regolatore.
1
Identificazione del modello
La serie di regolatori ATR142 prevede due versioni: facendo
riferimento alla tabella seguente è facile risalire al modello
desiderato.
Modelli con alimentazione 24…230 Vac/Vdc ±15% 50/60Hz - 4,6VA
ATR142-ABC
2 Relè (8A+5A) + 1 SSR
ATR142-ABC-T
2
2.1
1 Relè 8A + 1 SSR + RS485
Dati tecnici
Caratteristiche generali
Visualizzatori
4 display 0,40 pollici + 4 display 0,30 pollici
64 ATR 142 - Manuale d’uso
Temperatura di
esercizio
Materiale
temperatura funzionamento 0-45°C,
umidità 35..95uR%
IP65 (con guarnizione) su Frontale,
contenitore IP30 e morsettiere IP20
Policarbonato UL94V2 autoestinguente
Peso
100 g
Protezione
2.2
Caratteristiche hardware
AN1 Configurabile via
software
Termocoppie tipo:
K, S, R, J Compensazione
automatica del giunto
freddo da 0 … 50°C.
Ingresso
Termoresistenze:
analogici
PT100, PT500, PT1000,
Ni100, PTC1K, NTC10K
(β 3435K). Ingresso V/I:
0-10V, 0-20 o 4-20mA,
0-40mV. Ingresso Pot:
6KΩ, 150KΩ
2 relè (ATR142-ABC)
1 relè (ATR142-ABC-T)
Uscite relè Configurabili come
uscita comando e
allarme.
1 SSR Configurabile
Uscita SSR come uscita comando e
allarme.
Alimentazione a range
Alimentaesteso 24…230Vac/Vdc
zione
±15% 50/60Hz
Tolleranza (25°C)
+/-0.2 % ± 1 digit per
ingresso termocoppia,
termoresistenza e V/mA.
Precisione giunto
freddo 0.1°C/°C
Impedenza:
0-10V: Ri>110KΩ
0-20mA: Ri<5Ω
4-20mA: Ri<5Ω
0-40mV:Ri>1MΩ
Contatti:
Q1: 8A-250V~
per carichi resistivi
Q2: 5A-250V~
per carichi resistivi
12Vdc/30mA
Consumo: 4.6VA
Manuale d’suo - ATR 142 65
2.3
Caratteristiche software
Algoritmi
regolazione
Banda
proporzionale
Tempo integrale
ON-OFF con isteresi.
P, PI, PID, PD a tempo proporzionale
0...9999°C or °F
0,0...999,9 sec (0 esclude)
Tempo derivativo 0,0...999,9 sec (0 esclude)
Tuning manuale o automatico allarme selezionabile, protezione set comando e allarme,
Funzioni del
selezione funzioni da ingresso digitale, ciclo
regolatore
preprogrammato con Start/Stop.
Dimensioni e installazione
3
Frontal panel cut-out
Dima di foratura
28.5 x 70.5 mm
Suggested thickness
Spessore suggerito
2 ÷ 8 mm
Guarnizione per 32x74
Cod. 1600.00.082 (optional)
Gasket for 32x74
Memory Card (optional)
Cod. MEMORY 2100.30.005
42mm
inserimento
Memory Card
PIXSYS
42mm
insert
Memory Card
1
CN1
6
Memory Card (optional)
with battery
Cod. MEMORY 2100.30.003
U1
C1
6
35 mm
CN1
2
1
1
3
77 mm
66 ATR 142 - Manuale d’uso
7
53 mm
Collegamenti elettrici
4
Benché questo regolatore sia stato progettato
per resistere ai più gravosi disturbi presenti in
ambienti industriali è buona norma seguire la
seguenti precauzioni:
• Distinguere la linea di alimentazioni da quelle di potenza.
• Evitare la vicinanza di gruppi di teleruttori, contattori
elettromagnetici, motori di grossa potenza e comunque
usare gli appositi filtri.
• Evitare la vicinanza di gruppi di potenza, in particolare se a
controllo di fase.
Schema di collegamento
4.1
Di seguito sono riportati i collegamenti dei due modelli
disponibili.
PIXSYS
PIXSYS
ATRxxx-xx
2 wire
ATRxxx-xxT
2 wire
4/20mA
Power
3A 230V
Cosf 0.8
1A 230V
Cosf 0.8
Q1
SUPPLY
Q2
7
8
9
10
11
SUPPLY
Tc
-
12
1
1
Memory
ATR142-ABC
2
Q1
3
4
RS485
5
6
SSR
-
7
8
9
10
Tc
11
+
6
+
5
+VDC PTC/NTC
+
4
+
3
V/I
-
PT/NI100/1K
3A 230V
Cosf 0.8
+
2
+
SSR
1
1
-
10A 23a0V
Cosf 1
PT/NI100/1K
+VDC PTC/NTC
+
-
V/I
+
5A 230V
Cosf 1
+
10A 230V
Cosf 1
4/20mA
I
I
Power
12
Memory
ATR142-ABC-T
Alimentazione
2
24...230V
AC/DC
1
Alimentazione switching a range esteso
24…230 Vac/dc ±15% 50/60Hz – 3,5VA
Manuale d’suo - ATR 142 67
-
11
AN1 Analogue Input
Per termocoppie K, S, R, J.
• Rispettare la polarità
• Per eventuali prolunghe utilizzare
Shield/Schermo
cavo compensato e morsetti adatti alla
termocoppia utilizzata (compensati)
• Quando si usa cavo schermato lo
schermo deve essere collegato a terra
ad una sola estremità
Per termoresistenze PT100, NI100
Shield/Schermo • Per il collegamento a tre fili usare cavi
A
della stessa sezione.
• Per il collegamento a due fili cortocirB
cuitare i morsetti 10 e 12.
• Quando si usa cavo schermato, lo
schermo deve essere collegato a terra
C
ad una sola estremità
Tc
+
12
11
PT/NI100
10
12
RED 10
WHITE 11
RED 12
Shield/Schermo
11
PTC/NTC
10
9
+VDC
10
Shield/Schermo
Per termoresistenze NTC, PTC, PT500,
PT1000 e potenziometri lineari.
• Quando si usa cavo schermato lo
schermo deve essere collegato a terra
ad una sola estremità
-
11
V/I
+
12
Per segnali normalizzati in corrente e
tensione
• Rispettare la polarità
• Quando si usa cavo schermato lo
schermo deve essere collegato a terra
ad una sola estremità
68 ATR 142 - Manuale d’uso
Esempi di collegamento per ingressi normalizzati
12
Per segnali normalizzati in tensione
0….10V
• Rispettare le polarità
0...10V
11
12
Per segnali normalizzati in corrente
0/4….20mA con sensore a tre fili
Rispettare le polarità
C = Uscita sensore
B = Massa sensore
A = Alimentazione sensore
Per segnali normalizzati in corrente
0/4..20mA con sensore ad alimentazione
esterna
Rispettare le polarità
C = Uscita sensore
B = Massa sensore
C
0/4...20mA
11
B
9
A
PRESSURE TRANSMITTER
SENSORE DI PRESSIONE
12
C
0/4...20mA
11
B
EXTERNAL SUPPLY
ALIMENTAZIONE ESTERNA
PRESSURE TRANSMITTER
SENSORE DI PRESSIONE
12
C
Per segnali normalizzati in corrente
0/4..20mA con sensore a due fili
Rispettare le polarità
C = Uscita sensore
A = Alimentazione sensore
4...20mA
9
A
PRESSURE TRANSMITTER
SENSORE DI PRESSIONE
Ingresso Seriale
-
RS485, protocollo MODBUS-RTU
6
RS485
+
7
11
Shield/Schermo
Non usare resistenze di
terminazione
• Per reti con più di cinque strumenti
alimentare in bassa tensione
Manuale d’suo - ATR 142 69
Uscite relè
7
Q2
6
Portata contatti:
Q1: 8A, 250Vac,carico resistivo,105 operazioni. 30/3A, 250Vac, cosφ=0.3, 10 5
operazioni.
Q2: 5A, 250Vac,carico resistivo,105 operazioni. 20/2A, 250Vac, cosφ=0.3, 105
operazioni.
5
4
Q1
3
Uscita SSR
8
Uscita comando SSR portata 12V/30mA
SSR
9
Ingresso digitale
10
11
Ingresso digitale (parametro )
L’utilizzo dell’ingresso digitale è
possibile solo con sonde tipo Tc o 0…10V,
0/4…20mA e 0…40mV.
70 ATR 142 - Manuale d’uso
5
Configurazione EASYUP
Per semplificare il più possibile il lavoro di parametrizzazione
della catena di controllo, Pixsys presenta una nuova modalità
a codici che consente di configurare con un unico e semplice
passaggio ingressi sonda e/o uscite di comando.
La modalità EASYUP tramite il codice presente sulla documentazione tecnica allegata al sensore o all’attuatore (SSR,
valvola-motorizzata, ecc…) configura sullo strumento i
relativi parametri caratteristici (esempio per una PT100 il
parametro “SEN”, e la scala di utilizzo “Valore minimo di set”
e “Valore massimo”).
I codici possono essere utilizzati in sequenza per settare sia
ingressi che uscite comando o modalità di ritrasmissione del
segnale.
Manuale d’suo - ATR 142 71
6
Funzione dei visualizzatori e tasti
1
ATR 142
9
12
1 2 3
M T R
10
3
6.1
4
5
6
11
7
8
2
Indicatori numerici (display)
Normalmente visualizza il processo.
1
2
6.2
 In fase di configurazione visualizza il parametro in
inserimento.
Normalmente visualizza i setpoint. In fase di
 configurazione visualizza il valore del parametro
in inserimento.
Significato delle spie di stato (led)
2
Si accendono quando l’uscita comando è attiva.
Nel caso di comando valvola motorizzata è
acceso nel caso di apertura valvola e lampeggia
in chiusura.
Si accende quando l’allarme 1 è attivo.
5
3
Si accende quando l’allarme 2 è attivo.
6
M
7
T
8
R
Si accende all’attivazione della funzione “Manuale”.
Si accende quando il regolatore sta eseguendo un
ciclo di Tuning.
Si accende quando il regolatore comunica via
seriale.
3
1
4
72 ATR 142 - Manuale d’uso
6.3
Tasti
9
10
11
SET
12
FN C
7
7.1
• Decrementa il setpoint principale
• In fase di configurazione consente di scorrere i
parametri. Insieme al tasto SET li modifica.
• Premuto dopo il tasto SET decrementa i
setpoint di allarme.
• Incrementa il setpoint principale
• In fase di configurazione consente di scorrere i
parametri. Insieme al tasto SET li modifica.
• Premuto dopo il tasto SET Incrementa i
setpoint di allarme.
• Permette di visualizzare i setpoint di allarme.
• Permette di variare i parametri di configurazione.
• Permette di entrare nella funzione di lancio del
Tuning, selezione automatico/manuale.
• Permette di entrare/uscire dalla procedura di
configurazione.
Funzioni del regolatore
Modifica valore setpoint principale e
setpoint di allarme
Il valore dei setpoint può essere modificato da tastiera come segue:
Premere
Effetto
Eseguire
Incrementare o
La cifra sul display
9
diminuire il valore del
o
2 varia
setpoint principale
Visualizza setpoint di
10
SET
allarme sul display 1
Incrementare o
La cifra sul display
diminuire il valore del
11
o
2 varia
setpoint di allarme
Manuale d’suo - ATR 142 73
7.2
Auto-tune
La procedura di Tuning per il calcolo dei parametri di regolazione può essere manuale o automatica e viene selezionata
da parametro 46 .
7.3
Lancio del Tuning Manuale
La procedura manuale permette all’utente maggiore
flessibilità nel decidere quando aggiornare i parametri di
regolazione dell’argoritmo PID. La procedura può essere
attivata in due modi.
• Lancio del Tuning da tastiera:
Premere il tasto FNC finché il display 1 non visualizza la
scritta  con il display 2 su , premere
, il display
2 visualizza . Il led T si accende e la procedura ha inizio.
• Lancio del Tune da ingresso digitale:
Selezionare  su parametro 50  Alla prima attivazione dell’ingresso digitale (commutazione su fronte) il led T si
accende, alla seconda si spegne.
7.4
Tuning Automatico
Il Tuning automatico si attiva all’accensione dello strumento o
quando viene modificato il setpoint di un valore superiore al
35%. Per evitare overshoot il punto dove il regolatore calcola i
nuovi parametri PID è determinato dal valore di setpoint meno
il valore “Set Deviation Tune” (vedere Parametro 47 )
Per interrompere il Tuning lasciando invariati i valori PID, premere il tasto FNC finché il display 1 non visualizza la scritta 
e il display 2 visualizza . Premendo
, il display 2 visualizza
, il led T si spegne e la procedura termina.
74 ATR 142 - Manuale d’uso
7.5
Soft Start
Il regolatore all’accensione per raggiungere il setpoint segue
un gradiente di salita impostato in Unità (es. Grado / ora).
Impostare sul parametro 51  il valore di incremento in
Unità/Ora desiderato; alla successiva accensione lo strumento eseguirà la funzione Soft Start.
Non può essere abilitata la funzione Tuning automatico e
manuale se la funzione Soft Start è attiva.
7.6
Regolazione automatico/manuale per
controllo % uscita
Questa funzione permette di passare dal funzionamento automatico al comando manuale della percentuale dell’uscita.
Con il parametro 49  è possibile selezionare due modalità.
• Selezione  (Enable). Premendo il tasto FNC visualizza
la  scritta sul display 1, mentre sul display 2 appare
. Premere il tasto
per selezionare la modalità
manuale Con i tasti
e
variare la percentuale di
uscita.
Per tornare in automatico, con la stessa procedura, selezionare  sul display 2: subito si spegne il led M e il
funzionamento torna in automatico.
• Selezione  (enable stored). Abilita lo stesso funzionamento, ma con due importanti varianti:
• Nel caso di temporanea mancanza di tensione o comunque
dopo uno spegnimento, accendendo il regolatore verrà
mantenuto sia il funzionamento in manuale, sia il valore di
percentuale dell’uscita precedentemente impostato.
Manuale d’suo - ATR 142 75
• Nel caso di rottura del sensore durante il funzionamento
automatico, il regolatore si porterà in manuale mantenendo invariata la percentuale di uscita comando generata dal
PID subito prima della rottura.
7.7
Ciclo pre-programmato
Setpoint
Questa funzione permette di programmare un semplice
ciclo di lavoro temporizzato, e si abilita impostando 
nel parametro 48 : il processo raggiunge il setpoint1 in
base al gradiente impostato nel parametro 51 , poi sale
alla massima potenza verso il setpoint 2. Quando il processo
raggiunge il setpoint 2 resta in mantenimento per il tempo
impostato nel parametro 52  Allo scadere, il processo
raggiunge la temperatura ambiente in base al gradiente
impostato nel parametro 64  e poi l’uscita di comando
viene disabilitata e lo strumento visualizza .
Setpoint 2
Max Power
Max Potenza
Maintenance time
Mantenimento
Cooling
Raffreddamento
Setpoint 1
Rising gradient
Gradiente di salita
Time
Lo Start del ciclo avviene al ogni accensione dello strumento,
oppure da ingresso digitale se risulta abilitato per questo tipo
di funzionamento (vedi parametro 50 ).
76 ATR 142 - Manuale d’uso
7.8
Memory Card (opzionale)
È possibile duplicare parametri e setpoint da un regolatore ad
un altro mediante l’uso della Memory Card. Sono previste due
modalità:
• Con regolatore connesso all’alimentazione:
Inserire la Memory Card con regolatore spento. All’accensione il display 1 visualizza  e il display 2 visualizza
 (solo se nella Memory sono salvati valori corretti).
Premendo il tasto
il display 2 visualizza . Confermare
con il tasto FNC . Il regolatore carica i nuovi valori e riparte.
• Con regolatore non connesso all’alimentazione:
La memory card è dotata di batteria interna con autonomia per circa 1000
utilizzi. Inserire la memory card e premere il tasto di programmazione. Durante la scrittura dei parametri il led si
accende rosso, al termine della procedura si accende verde. È possibile ripetere la procedura senza particolari attenzioni.
Aggiornamento Memory Card.
Per aggiornare i valori della Memory seguire il procedimento descritto nella prima modalità, impostando  sul
display 2 in modo da non caricare i parametri sul regolatore210.
Entrare in configurazione e variare almeno un parametro.
Uscendo dalla configurazione il salvataggio sarà automatico.
10
Nel caso in cui all’accensione il regolatore non visualizzi  significa
che non ci sono dati salvati nella Memory Card, ma è possibile ugualmente
aggiornarne i valori.
Manuale d’suo - ATR 142 77
7.9
Caricamento valori di default
Questa procedura permette di ripristinare le impostazioni di
fabbrica dello strumento.
Premere
Effetto
Eseguire
Su display 1 compare
 con la 1^ cifra
FN C
1
lampeggiante, mentre
per 3 sec. sul display 2 compare

2
3
o
Si modifica la cifra
lampeggiante si passa Inserire la password
alla successiva con il 
tasto SET
Lo strumento carica
SET
le impostazioni di
per
conferma fabbrica
Spegnere e
riaccendere lo
strumento
7.10 Funzione LATCH ON
Per l’impiego con ingresso Pot.1 (pot. 6KΩ) e Pot.2 (pot.150KΩ)
e con ingressi normalizzati (0…10V, 0...40mV, 0/4…20mA), è
possibile associare il valore di inizio scala (parametro 6 )
alla posizione di minimo del sensore e quello di fine scala
(parametro 7 ) alla posizione di massimo del sensore
(parametro 8  configurato come ). È inoltre possibile
fissare il punto in cui lo strumento visualizzerà 0 (mantenendo
comunque il campo scala compreso tra  e  ) tramite
l’opzione di “zero virtuale” impostando  oppure 
nel parametro 8  Se si imposta , lo zero virtuale
andrà reimpostato dopo ogni accensione dello strumento; se
si imposta  lo zero virtuale resterà fisso una volta tarato.
Per utilizzare la funzione LATCH ON configurare come desi78 ATR 142 - Manuale d’uso
derato il parametro 11 Per la procedura di taratura fare
riferimento alla seguente tabella:
Premere
Effetto
Eseguire
Posizionare il sensore
Esce dalla configuraziosul valore minimo
1
FNC ne parametri. Il display 2
di funzionamento
visualizza la scritta .
(associato a )
Posizionare il sensore sul
Fissa il valore sul minimo. valore massimo di fun2
Il display visualizza  zionamento (associato
a )
Per uscire dalla
procedura standard
Fissa il valore sul
premere FNC .
3
massimo. Il display
Nel caso di impostazione
visualizza 
con “zero virtuale”
posizionare il sensore
nel punto di zero.
Fissa il valore di zero
virtuale. Il display
visualizza  NB: nel
Per uscire dalla procedu4 SET caso di selezione 
ra tenere premuto FNC .
la procedura al punto
4 va eseguita ad ogni
ri-accensione.
Min
11
Max
Zero
La procedura di taratura parte uscendo dalla configurazione dopo aver
variato il parametro.
Manuale d’suo - ATR 142 79
7.11 Funzioni da Ingresso digitale
L’utilizzo dell’ingresso digitale abilita alcune funzioni utili
a semplificare l’operatività del regolatore. Selezionare la
funzione desiderata sul parametro 50 
• Funzione Hold: si abilitata impostando  o 
e permette di bloccare la lettura delle sonde quando
l’ingresso digitale è attivo. Risulta utile quando la misura
oscilla molto sui valori meno significativi. Durante la fase di
blocco il display 2 lampeggia visualizzando .
• Abilita/disabilita il Tuning da ingresso digitale se il parametro  è impostato su .
• Abilita regolazione con  o 
• Passa da funzionamento automatico a manuale se  è
impostato su  o 
• Start del ciclo preprogrammato con (vedi par. 7.7).
• È possibile utilizzare l’ingresso digitale per la funzione di
“Cambio Setpoint”. Questo funzionamento è utile nel caso
ci siano da 2 a 4 soglie di lavoro che si vogliono richiamare
da pulsante senza dover agire sui tasti freccia durante il
funzionamento dell’impianto. Per abilitare la funzionalità
agire sul parametro 48 , selezionando il numero di
setpoint desiderati (n. Thresholds switch). Questi potranno
essere impostati durante il funzionamento premendo il
tasto SET .
NB: le funzioni da ingresso digitale non sono disponibili con
sonde PT100, NI100, NTC, PTC, PT500, PT1000 e potenziometri
lineari.
80 ATR 142 - Manuale d’uso
7.12 Funzionamento in doppia azione
(caldo-freddo)
L’ATR142 è adatto alla regolazione anche su impianti che
prevedano un’azione combinata caldo-freddo.
L’uscita di comando deve essere configurata in PID caldo
(  =  e  maggiore di 0), e uno degli allarmi ( o
) deve essere configurato come . L’uscita di comando
va collegata all’attuatore responsabile dell’azione caldo,
l’allarme comanderà invece l’azione refrigerante.
I parametri da configurare per il PID caldo sono:
 =  Tipo azione uscita di comando (Caldo)
: Banda proporzionale azione caldo
 : Tempo integrale azione caldo ed azione freddo
: Tempo derivativo azione caldo ed azione freddo
: Tempo di ciclo azione caldo
I parametri da configurare per il PID freddo sono
(azione associata, per esempio, all’allarme1):
 =  Selezione Allarme1 (Cooling)
 : Moltiplicatore di banda proporzionale
: Sovrapposizione / Banda morta
: Tempo di ciclo azione freddo
Il parametro  (che varia da 1.00 a 5.00) determina la banda proporzionale dell’azione refrigerante secondo la formula:
Banda proporzionale azione refrigerante =  * 
Si avrà così una banda proporzionale per l’azione refrigerante
che sarà uguale a quella dell’azione caldo se  = 1.00, o 5
volte più grande se  = 5.00.
Tempo integrale e Tempo derivativo sono gli stessi per
entrambe le azioni.
Manuale d’suo - ATR 142 81
Il parametro  determina la sovrapposizione in
percentuale tra le due azioni. Per gli impianti in cui l’uscita
riscaldante e l’uscita refrigerante non devono mai essere
attive contemporaneamente si configurerà una Banda morta
(  ≤ 0), viceversa si potrà configurare una sovrapposizione (  > 0).
La figura seguente riporta un esempio di PID doppia azione
(caldo-freddo) con  = 0 e  = 0.
 x  (COOL)
 < 0
SPV
PV
 (HEAT)
ATTIVO
ACTIVE
ATTIVO
ACTIVE
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
 x  (COOL)
 = 0
SPV
 (HEAT)
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
82 ATR 142 - Manuale d’uso
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
 x  (COOL)
 > 0
SPV
 (HEAT)
PV
ATTIVO
ACTIVE
ATTIVO
ACTIVE
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
Il parametro  ha lo stesso significato del tempo di ciclo per
l’azione caldo  Il parametro  (Cooling Fluid) pre-seleziona il moltiplicatore di banda proporzionale  ed il tempo di
ciclo  del PID freddo in base al tipo di fluido refrigerante:
 Tipo di fluido refrigerante 

Air
1.00
10

Oil
1.25
4

Water
2.50
2

Una volta selezionato il parametro , i parametri ,
 e  possono essere comunque modificati.
8
Funzioni Timer
Le funzionalità legate al timer vengono abilitate sul parametro 63  Per variare la durata del tempo di conteggio
seguire i punti elencati nella seguente tabella:
Premere
Effetto
Eseguire
Premere fino alla
visualizzazione di 
1
SET
o  sul display1.
Incrementare o
La cifra sul display
2
diminuire il tempo
o
2 varia
del timer selezionato
Manuale d’suo - ATR 142 83
Di seguito la descrizione delle varie modalità di funzionamento
dei timer.
8.1
Singolo Timer
Questa modalità abilita un timer con tempo impostabile
dall’utente. Per il funzionamento del singolo timer impostare
il parametro 63  come segue:
•  (Single Timer Seconds) base tempi in secondi (mm.ss)
•  (Single Timer Minutes) base tempi in minuti (hh.mm)
Per far partire o fermare il timer tenere premuto il tasto FNC
per 1 “. Durante il conteggio si accende il led R e il display
2 visualizza il tempo in decremento. Allo scadere del timer il
led R si spegne e il display 2 lampeggia mostrando il tempo
impostato, fino alla pressione di un tasto. È possibile fare lo
start/stop del timer anche da ingresso digitale impostando
 sul parametro 50 
8.2
Doppio Timer
Questa modalità abilita due timer con tempo impostabile
dall’utente: i timer non possono essere messi in start contemporaneamente.
Per il funzionamento del doppio timer impostare il parametro
63    come segue:
•   (Double Timer Seconds) base tempi in secondi (mm.ss)
•    (Double Timer Minutes) base tempi in minuti (hh.mm)
84 ATR 142 - Manuale d’uso
Per la procedura di start dei timer far riferimento alla tabella
seguente:
PreEffetto
Eseguire
mere
Premere fino alla
1
FNC visualizzazione di 
o  sul display1.
Start del timer. Il display Tornare al punto 1 e una
2 visualizza il tempo in
volta selezionato il timer
decremento e si accende in start premere
per
2
R
(fisso per timer 1 e Wfermare il conteggio. Il
il led
R
lampeggiante per timer2) led
si spegne
Allo scadere del timer il led R si spegne e il display 2 lampeggia mostrando il tempo impostato, fino alla pressione di un
tasto. Nella modalità doppio timer non è possibile abilitare lo
start/stop da ingresso digitale.
8.3
Doppio Timer Sequenziale
Questa modalità abilita due timer con tempo impostabile
dall’utente. Allo scadere del timer 1 parte automaticamente
il conteggio del timer2: una volta scaduto anche il timer 2 il
conteggio si ferma.
Per il funzionamento del doppio timer sequenziale impostare
il parametro 63  come segue:
•  (Double Sequential Timer Seconds) base tempi in
secondi (mm.ss)
•  (Double Sequential Timer Minutes) base tempi in
minuti (hh.mm)
Per far partire o fermare il timer tenere premuto il tasto FNC per 1“.
Durante il conteggio si accende il led R (fisso per timer 1 e
Manuale d’suo - ATR 142 85
lampeggiante per timer 2) e il display 2 visualizza il tempo in
decremento. Lo start avviene sempre sul timer 1. Allo scadere del
timer il led R si spegne e il display 2 torna alla visualizzazione
del setpoint. È possibile fare lo start/stop del timer anche da
ingresso digitale impostando  sul parametro 50 
8.4
Doppio Timer Loop
Questa modalità abilita due timer con tempo impostabile
dall’utente. Allo scadere di un timer parte automaticamente
l’altro: la sequenza si ripete ciclicamente.
Per il funzionamento del doppio timer loop impostare il
parametro 63  come segue:
•  (Double Timer Loop Seconds) base tempi in secondi
(mm.ss)
•  (Double Timer Loop Minutes) base tempi in minuti
(hh.mm)
Per far partire o fermare il timer tenere premuto il tasto FNC per 1“.
Durante il conteggio si accende il led R (fisso per timer 1 e
lampeggiante per timer 2) e il display 2 visualizza il tempo in
decremento. Lo start avviene sempre sul timer 1.
È possibile fare lo start/stop del timer anche da ingresso
digitale impostando  sul parametro 50 
8.5
Associazione Timer - Allarmi
È possibile associare gli allarmi (uscite relè o SSR) ai timer
mediante i parametri 23   e 31  . Per la logica di
funzionamento degli allarmi correlati ai timer fare riferimento
alla seguente tabella:
86 ATR 142 - Manuale d’uso
Selezione
par. 23 o 31
Descrizione

Allarme attivo durante lo start del
Timer 1 Start Alarm timer 1
Allarme attivo allo scadere del timer
1: resta attivo fino alla pressione di un

Timer 1 End Alarm tasto. Non funziona in modalità doppio
timer sequenziale e loop.

Timer 1 Warning
Expiring
Allarme attivo gli ultimi 5“ del timer 1.
Allarme attivo durante lo start del

Timer 2 Start Alarm timer 2
Allarme attivo allo scadere del timer
2: resta attivo fino alla pressione di un

Timer 2 End Alarm tasto. Non funziona in modalità doppio
timer sequenziale e loop.

Timer 2 Warning
Expiring
Allarme attivo gli ultimi 5“ del timer 2.
Allarme attivo durante lo start del timer

Timer 1-2 Start Alarm 1 e 2
Allarme attivo allo scadere del timer 1 e
2: resta attivo fino alla pressione di un

Timer 1-2 End Alarm tasto. Non funziona in modalità doppio
timer sequenziale e loop.

Timer 1-2 Warning Allarme attivo gli ultimi 5“ del timer 1 e 2.
expiring
Manuale d’suo - ATR 142 87
9
9.1
Comunicazione Seriale
Slave
L’ATR142-ABC-T con RS485 può ricevere e trasmettere dati via
seriale tramite protocollo MODBUS RTU. Il dispositivo funziona
come slave se il parametro 59  è impostato su . Questa
funzione permette il controllo di più regolatori collegati ad un
sistema di supervisione. Ciascuno strumento risponderà ad
un’interrogazione del Master solo se questa contiene l’indirizzo
uguale a quello contenuto nel parametro  Gli indirizzi
permessi vanno da 1 a 254 e non devono esserci regolatori con
lo stesso indirizzo sulla stessa linea.
L’indirizzo 255 può essere usato dal Master per comunicare con
tutte le apparecchiature collegate (modalità broadcast), mentre
con 0 tutti i dispositivi ricevono il comando, ma non è prevista
alcuna risposta. L’ATR142 può introdurre un ritardo (in millisecondi) della risposta alla richiesta del Master. Tale ritardo deve
essere impostato sul parametro 58  Ad ogni variazione
dei parametri lo strumento salva il valore in memoria EEPROM
(100000 cicli di scrittura), mentre il salvataggio dei setpoint
avviene con un ritardo di 10 secondi dall’ultima modifica.
NB: Modifiche apportate a Word diverse da quelle riportate
nella tabella seguente possono causare mal funzionamenti
dello strumento.
88 ATR 142 - Manuale d’uso
Caratteristiche protocollo Modbus RTU
Selezionabile da parametro 56
 4800bit/sec
 9600bit/sec
Baud-rate
 19200bit/sec
 28800bit/sec
 38400bit/sec
 57600bit/sec
Formato
8, N, 1 (8bit, no parità, 1 stop)
Funzioni
supportate
WORD READING (max 20 word) (0x03, 0x04)
SINGLE WORD WRITING (0x06)
MULTIPLE WORDS WRITING (max 20 word)
(0x10)
Si riporta di seguito l’elenco di tutti gli indirizzi disponibili, dove:
RO = Read Only
Modbus
address
0
1
5
6
50
51
R/W = Read/Write
Descrizione
Tipo dispositivo
Versione software
Address slave
Versione boot
Indirizzamento automatico
Confronto codice impianto
WO = Write Only
Read
Write
RO
RO
R/W
RO
WO
WO
Reset
value
EEPROM
EEPROM
EEPROM
EEPROM
-
Manuale d’suo - ATR 142 89
500
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
1012
Caricamento valori di default:
9999 ripristina tutti i valori
9998 ripristina tutti i valori escluso
baud-rate e address slave
9997 ripristina tutti i valori escluso
address slave
9996 ripristina tutti i valori escluso
baud-rate
Processo (gradi con decimo per
sensori di temperatura; digit per
sensori normalizzati)
Setpoint1
Setpoint2
Setpoint3
Setpoint4
Allarme1
Allarme2
Setpoint gradiente
Stato uscite (0=off, 1=on)
Bit 0 = relè Q1
Bit 1 = relè Q2
Bit 2 = SSR
Percentuale uscita caldo (0-10000)
Percentuale uscita freddo (0-10000)
Stato allarmi (0=assente, 1=presente)
Bit0 = Allarme 1
Bit1 = Allarme 2
Riarmo manuale: scrivere 0 per
riarmare tutti gli allarmi.
In lettura
(0=non riarmabile, 1=riarmabile):
Bit0 = Allarme 1
90 ATR 142 - Manuale d’uso
WO
0
RO
-
R/W
R/W
R/W
R/W
R/W
R/W
RO
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
RO
0
RO
RO
0
0
RO
0
WO
0
1013
1014
1015
1016
1017
1018
1019
1100
1101
1102
1103
Flags errori
Bit0 = Errore scrittura eeprom
Bit1 = Errore lettura eeprom
Bit2 = Errore giunto freddo
Bit3 = Errore processo (sonda)
Bit4 = Errore generico
Bit5 = Errore hardware
Bit6 = Master off-line
Bit7 = Taratura mancante
Temperatura giunto freddo
(gradi con decimo)
Start/Stop
0= regolatore in STOP
1= regolatore in START
Blocco conversione ON/OFF
0= Blocco conversione off
1= Blocco conversione on
Tuning ON/OFF
0= Tuning off
1= Tuning on
Selezione automatico/manuale
0=automatico
1=manuale
Tempo OFF LINE* (millisecondi)
Processo visualizzato (decimale
come sul display)
Setpoint1 visualizzato (decimale
come sul display)
Setpoint2 visualizzato (decimale
come sul display)
Setpoint3 visualizzato (decimale
come sul display)
RO
0
RO
-
R/W
0
R/W
0
R/W
0
R/W
0
R/W
0
RO
-
R/W EEPROM
R/W EEPROM
R/W EEPROM
Manuale d’suo - ATR 142 91
1104
1105
1106
1107
1108
1109
1110
1111
2001
...
2064
3000
3001
...
3008
3009
...
3016
3017
Setpoint4 visualizzato (decimale
come sul display)
Allarme1 visualizzato (decimale
come sul display)
Allarme2 visualizzato (decimale
come sul display)
Setpoint gradiente (decimale come
sul display)
Percentuale uscita caldo (0-1000)
Percentuale uscita caldo (0-100)
Percentuale uscita freddo (0-1000)
Percentuale uscita freddo (0-100)
Parametro 1
...
Parametro 64
Disabilitazione controllo macchina
da seriale**
Prima word display1 (ascii)
…..
Ottava word display1 (ascii)
Prima word display2 (ascii)
…..
Ottava word display2 (ascii)
Word LED
Bit 0 = LED 1
Bit 1 = LED 2
Bit 2 = LED 3
Bit 3 = LED MAN
Bit 4 = LED TUN
Bit 5 = LED REM
92 ATR 142 - Manuale d’uso
R/W EEPROM
R/W EEPROM
R/W EEPROM
RO
EEPROM
RO
RO
RO
RO
R/W
...
R/W
0
0
0
0
EEPROM
...
EEPROM
WO
0
R/W
R/W
R/W
R/W
R/W
R/W
0
0
0
0
0
0
R/W
0
3018
3019
3020
3021
9.2
Word tasti (scrivere 1 per assumere
il controllo dei tasti)
Bit 0 =
Bit 1 =
Bit 2 = SET
Bit 3 = FNC
Word uscite seriale
Bit 0 = relè Q1
Bit 1 = relè Q2
Bit 2 = uscita SSR
Word stato uscite seriale in caso
di off-line
Bit 0 = relè Q1
Bit 1 = relè Q2
Bit 2 = uscita SSR
Word processo seriale
R/W
0
R/W
0
R/W
0
R/W
0
Master
Il dispositivo funziona come master se il valore impostato sul
parametro 59  è diverso da .
9.2.1 Modalità master in ritrasmissione
In questa modalità lo strumento scrive il valore da ritrasmettere all’indirizzo impostato sul parametro 60 , su altri
slave che hanno ID uguale al valore impostato sul parametro
57 . Per la ritrasmissione dei setpoint dopo l’avvenuta
scrittura sullo slave, l’ATR142 inizia a leggere la word selezionata: in questo modo un’eventuale variazione del valore sullo
slave viene appreso anche dal master. Due interrogazioni
successive vengono ritardate del tempo impostato su parametro 57 .
Manuale d’suo - ATR 142 93
Nella seguente tabella sono riportate le selezioni che permettono il funzionamento master in ritrasmissione e la relativa
grandezza ritrasmessa.


Descrizione
Scrive il valore del processo
Write Process

Scrive e legge il valore del setpoint di
Read/Write
comando
Command Setpoint

Scrive la percentuale di uscita calcolata
dal P.I.D. (Range 0-10000)
Write Output
Percentage
Scrive e legge il valore del setpoint

Read/Write Alarm 1 dell’allarme 1
Il valore letto/scritto può essere riscalato seguendo la proporzione proposta nella seguente tabella:
limiti valore ingresso limiti valore riscalato

Min
Max
Min
Max

Write
Process

Read/Write
Command
Setpoint

Write
Output
Percentage






Lower Limit Upper Limit
Lower
Upper
Retransmis- RetransmisLimit Input Limit Input
sion
sion

Lower
Limit
Setpoint
0
94 ATR 142 - Manuale d’uso

Upper Lower Limit Upper Limit
Limit
Retransmis- RetransmisSetpoint
sion
sion

10000

Lower Limit Upper Limit
Retransmis- Retransmission
sion

Read/Write
Alarm 1

Lower
Limit
Setpoint



Upper Lower Limit Upper Limit
Limit
Retransmis- RetransmisSetpoint
sion
sion
Il valore in ingresso (compreso tra i limiti minimo e massimo)
viene trasformato in maniera lineare nel valore in ritrasmissione
compreso tra i valori minimo e massimo in uscita. La riscalatura
non viene eseguita se i parametri  e  hanno lo stesso
valore.
9.2.2 Modalità master processo remoto
Per abilitare questo funzionamento bisogna impostare 
sul parametro 59 . In questa modalità l’ATR142 legge un
valore da remoto e lo imposta come processo. Lo slave deve
avere un ID uguale a quello impostato sul parametro 57 
e la word da leggere è selezionata sul parametro 60 .
Due interrogazioni successive vengono ritardate del tempo
impostato su parametro 57  Il valore letto può essere
riscalato seguendo la proporzione proposta nella seguente
tabella:
Limiti valore letto
Limiti valore riscalato

Min
Max
Min
Max


Read
Process

Lower
Upper


Limit Re- Limit Re- Lower Limit Upper Limit
Input
Input
transmis- transmission
sion
Manuale d’suo - ATR 142 95
10 Configurazione
10.1 Modifica parametro di configurazione
Per parametri di configurazione vedi il paragrafo 11.
Premere
Effetto
Eseguire
Su display 1 compare
 con la 1° cifra
FN C
1
lampeggiante, mentre
per 3 sec. sul display 2 compare
.
Si modifica la cifra
lampeggiante si passa Inserire la password
2
o
alla successiva con il 
tasto SET
3
4
Su display 1 compare
SET
il primo parametro e
per
conferma sul secondo il valore.
Scorre i parametri
o
SET
5
+
o
6
FN C
Si incrementa o
decrementa il
valore visualizzato
premendo prima SET
e poi un tasto freccia.
Fine variazione
parametri di
configurazione.
Il regolatore esce dalla
programmazione.
96 ATR 142 - Manuale d’uso
Inserire il nuovo dato
che verrà salvato
al rilascio dei tasti.
Per variare un altro
parametro tornare al
punto 4
11
Tabella parametri di configurazione
L’elenco dei parametri sotto riportato è completo; alcuni di
questi non appariranno sui modelli che non dispongono delle
relative risorse hardware.
1
    Command Output
selezione tipo uscita di comando.


> Default (Parametro di fabbrica)









ATR142-ABC
Command
Q2
Q1
Alarm 1
Q1
Q2
Q1
SSR

Q1(apri) Q2(chiudi)
ATR142-ABC-T
Command
Q1
SSR
Q1(apri) SSR(chiudi)
Alarm 2
SSR
SSR
Q2
-
Alarm 1
SSR
Q1
-
2  Sensor
configurazione ingresso analogico.
 Tc-K -260…1360°C > Default
 Tc-S -40…1760°C
 Tc-R -40…1760°C
 Tc-J -200…1200°C

PT100 -200…600°C
 PT100 -200…140°C
Manuale d’suo - ATR 142 97











NI100 -60…180°C
NTC10K -40…125°C
PTC1K -50…150°C
PT500 -100…600°C
PT1000 - 100…600°C
0…10Volt
0…20mA
4…20mA
0…40mVolt
Potenz.Max 6KΩ F.S.
Potenz.Max 150KΩ F.S.
3  
Decimal Point
seleziona il tipo di decimale visualizzato.

> Default



4  Lower Limit Setpoint
limite inferiore setpoint.
-999…+9999 [digit12] (gradi.decimi
temperatura) Default: 0.
5  Upper Limit Setpoint
limite superiore setpoint.
-999…+9999 [digit12] (gradi.decimi
temperatura) Default: 1750.
per
sensori
di
per
sensori
di
6  Lower Linear Input
limite inferiore range AN1 solo normalizzati.
-999…+9999 [digit12] Default: 0.
98 ATR 142 - Manuale d’uso
7  Upper Linear Input
limite superiore range AN1 solo normalizzati.
-999…+9999 [digit12] Default: 1000.
8  Latch On Function
impostazione automatica dei limiti per ingressi lineari.

Disabled > Default
 Standard
 Virtual Zero Stored
  Virtual Zero Initialized
9  Offset Calibration
calibrazione offset. Numero che si somma al processo
visualizzato (normalmente corregge il valore di temperatura
ambiente).
-999…+1000 [digit12] per sensori normalizzati e
potenziometri.
-99.9…+100.0 (gradi.decimi per sensori di temperatura). >
Default: 0.0.
10  Gain Calibration
calibrazione guadagno. Valore che si moltiplica al processo
per eseguire calibrazioni sul punto di lavoro.
-99.9%…+100.0% > Default: 0.0
11  Action type
tipo di regolazione
 Caldo (N.A.) > Default
 Freddo (N.C.)
 Blocca comando sopra SPV.
12  Command Reset
tipo di riarmo del contatto di comando (sempre automatico
in funzionamento PID).
Manuale d’suo - ATR 142 99
 Automatic Reset > Default
 Manual Reset
 Manual Reset Stored
13  Command State Error
stato del contatto per l’uscita di comando in caso di errore.

> Default

14  Command Led
definisce lo stato del led OUT1 in corrispondenza del
relativo contatto.


> Default
15  Command Hysteresis
isteresi in ON/OFF o banda morta in P.I.D.
-999…+999 [digit12], (gradi.decimi per
temperatura) > Default: 0.0
sensori
di
16  Command Delay
ritardo comando (solo in funzionamento ON/OFF).(In caso
di servo valvola funziona anche in PID e rappresenta il
ritardo tra l’apertura e la chiusura dei due contatti).
-180…+180 secondi, decimi di secondo in caso di servo valvola.
Negativo: ritardo in fase di spegnimento.
Positivo: ritardo in fase di accensione.
Default: 0.
17  Command Setpoint Protection
consente o meno di variare il valore del setpoint di
comando.
 > Default
 Bloccato
100 ATR 142 - Manuale d’uso
18 
Proportional Band
Banda proporzionale.
Inerzia del processo in unità (Es.: se temperatura in °C).
0 on/off se  uguali a 0. > Default
1-9999 [digit12], (gradi per sensori di temperatura).
19 
Integral Time
inerzia del processo in secondi.
0.0-999.9 sec. (0 integrale disabilitato) > Default: 0.
20 
Derivative Time
normalmente ¼ del tempo integrale.
0.0-999.9 sec. (0 integrale disabilitato) > Default: 0.
21 
Cycle Time
(per PID su teleruttore 10/15 sec, per PID su SSR 1 sec)
o tempo servo (valore dichiarato da produttore del
servomotore).
0.1-300.0 sec. > Default: 10.0.
Per servo-valvole il tempo minimo impostabile è 1.0 sec.
22  Output Power Limit
limite del segnale di comando.
10-100 % > Default: 100
23  Alarm
Selezione allarme 1. L’intervento dell’allarme è associato a AL1.

Disabled > Default
 Absolute Alarm (vedi par. 12)
 Band Alarm (vedi par. 12)
 High Deviation Alarm (vedi par. 12)
 Low Deviation Alarm (vedi par. 12)
12
La visualizzazione del punto decimale dipende dall’impostazione del
parametro  e del parametro 
Manuale d’suo - ATR 142 101












Absolute Command setpoint Alarm
Start Alarm, Active in Run
Cooling
Timer 1 Start Alarm
Timer 1 End Alarm
Timer 1 Warning Expiring
Timer 2 Start Alarm
Timer 2 End Alarm
Timer 2 Warning Expiring
Timer 1-2 Start Alarm
Timer 1-2 End Alarm
Timer 1-2 Warning Expiring
24  Alarm 1 State Output
contatto uscita allarme 1 e tipo intervento
 (n.o. start) Normalmente aperto attivo allo start >
Default
 (n.c. start) Normalmente chiuso attivo allo start.
 (n.o. threshold) Normalmente aperto attivo al
raggiungimento dell’allarme13.
 (n.c. threshold) Normalmente chiuso attivo al
raggiungimento dell’allarme13.
25  Alarm 1 Reset
tipo di riarmo del contatto dell’allarme 1.
 Automatic Reset > Default
 Manual Reset
 Manual Reset Stored
13
All’accensione l’uscita è inibita se lo strumento è in condizione di allarme. Si attiva solo quando rientrato dalla condizione d’allarme, questa si
ripresenta.
102 ATR 142 - Manuale d’uso
26  Alarm 1 State Error
stato del contatto per l’uscita di allarme 1 in caso di errore.

> Default

27  Alarm 1 Led
definisce lo stato del led OUT2 in corrispondenza del
relativo contatto.


> Default
28  Alarm 1 Hysteresis
-999…+999 [digit14], (gradi.decimi
temperatura).
per
sensori
di
29  Alarm 1 Delay
-180…+180 Sec. > Default: 0.
Negativo: ritardo in fase di uscita dall’allarme.
Positivo: ritardo in fase di entrata dell’allarme.
30  Alarm 1 Setpoint Protection
protezione set allarme 1. Non consente all’utente di variare
il setpoint.
 > Default
 Bloccato
 Bloccato e Nascosto
31  Alarm 2
selezione allarme 2. L’intervento dell’allarme è associato a AL2.

Disabled > Default
 Absolute Alarm
 Band Alarm
14
La visualizzazione del punto decimale dipende dall’impostazione del
parametro  e del parametro 
Manuale d’suo - ATR 142 103














High Deviation Alarm
Low Deviation Alarm
Absolute Command setpoint Alarm
Start Alarm, Attivo in Run
Cooling
Timer 1 Start Alarm
Timer 1 End Alarm
Timer 1 Warning Expiring
Timer 2 Start Alarm
Timer 2 End Alarm
Timer 2 Warning Expiring
Timer 1-2 Start Alarm
Timer 1-2 End Alarm
Timer 1-2 Warning Expiring
32  Alarm 2 State Output
contatto uscita allarme 2 e tipo intervento
 (n.o. start) Normalmente aperto attivo allo start >
Default
 (n.c. start) Normalmente chiuso attivo allo start.
 (n.o. threshold) Normalmente aperto attivo al
raggiungimento dell’allarme15
 (n.c. threshold) Normalmente chiuso attivo al
raggiungimento dell’allarme15
33  Alarm 2 Reset
Tipo di riarmo del contatto dell’allarme 2.
 Automatic Reset > Default
 Manual Reset
 Manual Reset Stored
15
All’accensione l’uscita è inibita se lo strumento è in condizione di allarme. Si attiva solo quando rientrato dalla condizione d’allarme, questa si
ripresenta.
104 ATR 142 - Manuale d’uso
34  Alarm 2 State Error
stato del contatto per l’uscita di allarme 2 in caso di errore.

> Default

35  Alarm 2 Led
definisce lo stato del led OUT2 in corrispondenza del
relativo contatto.


> Default
36  Alarm 2 Hysteresis
-999…+999 [digit16], (gradi.decimi
temperatura). > Default: 0.
per
sensori
di
37  Alarm 2 Delay
-180…+180 Sec. > Default: 0.
Negativo: ritardo in fase di uscita dall’allarme.
Positivo: ritardo in fase di entrata dell’allarme.
38  Alarm 2 Setpoint Protection
protezione set allarme 2.
Non consente all’operatore di variare il valore impostato.
 > Default
 Bloccato
 Bloccato e nascosto
39  Cooling Fluid
tipo di fluido refrigerante

Air > Default

Oil

Water
Manuale d’suo - ATR 142 105
40  Proportional Band Multiplier
1.00-5.00 > Default: 1.00.
41 . Overlap/Dead Band
sovrapposizione/Banda Morta -20.0-50.0% > Default: 0.
42  Cooling Cycle Time
tempo ciclo per uscita refrigerante
1-300 sec. > Default: 10.
43  Conversion Filter
filtro adc: numero di medie effettuate sulle conversioni
analogico-digitali.

Disabled
 2 Samples Mean
 3 Samples Mean
 4 Samples Mean
 5 Samples Mean
 6 Samples Mean
 7 Samples Mean
 8 Samples Mean
 9 Samples Mean
 10 Samples Mean > Default
 11 Samples Mean
 12 Samples Mean
 13 Samples Mean
 14 Samples Mean
 15 Samples Mean
44  Conversion Frequency
frequenza di campionamento del convertitore analogico-digitali.
 242 Hz Max velocità di conversione ADC
 123 Hz
 62 Hz
106 ATR 142 - Manuale d’uso










50 Hz
39 Hz
33.2 Hz
19.6 Hz
16.7 Hz > Default
12.5 Hz
10 Hz
8.33 Hz
6.25 Hz
4.17 Hz Min. velocità di conversione ADC
45  Visualization Filter
filtro in visualizzazione. Rallenta l’aggiornamento del display
mantenendo invariata la velocità di conversione ADC.

Disabled
 Pitchfork filter > Default
 First Order
 First Order with Pitchfork
 2 Samples Mean
 3 Samples Mean
 4 Samples Mean
 5 Samples Mean
 6 Samples Mean
 7 Samples Mean
 8 Samples Mean
 9 Samples Mean
 10 Samples Mean
46  Tune
selezione tipo autotuning

Disabled > Default
 Automatic. Calcolo parametri PID all’accensione e
al variare del set
 Manual. Lanciato dai tasti o da ingresso digitale.
Manuale d’suo - ATR 142 107
47  Setpoint Deviation Tune
seleziona la deviazione dal setpoint di comando per la
soglia usata dall’ autotuning per il calcolo dei parametri PID.
0-5000 [digit16], (gradi.decimi per sensori di temperatura) >
Default: 10.
48  Operative Mode
selezione funzionamento
 Controller > Default
 Programmed Cycle
 2 Thresholds Switch
 2 Thresholds Switch Impulsive
 3 Thresholds Switch Impulsive
 4 Thresholds Switch Impulsive
49  Automatic/Manual
abilita la selezione automatico/manuale.

Disabled > Default

Enabled
 Enabled Stored
50  Digital Input
funzionamento ingresso digitale.
Selezione Par. 48 deve essere  oppure 

Disabled > Default
 Start/Stop
 Run n.o.
 Run n.c.
 Lock Conversion n.o. (Blocco della visualizzazione
con contatto Normalmente aperto)
 Lock Conversion n.c. (Blocco della visualizzazione
con contatto Normalmente chiuso)
 Tune > Manual
 Automatic Manual impulse
 Automatic Manual Contact
108 ATR 142 - Manuale d’uso
 Timer 1 Start Stop
51  Gradient
gradiente di salita per Soft Start o ciclo preprogrammato.
0 Disabilitato > Default: 0.
1-9999 Digit/ora16 (gradi/ora con visualizzazione del decimo
se temperatura)
52  Maintenance Time
tempo mantenimento per ciclo preprogrammato.
00.00-24.00 hh.mm > Default: 00.00
53  User Menu Cycle Programmed
permette di modificare gradiente di salita e tempo di
mantenimento dal menù utente in funzionamento ciclo
preprogrammato.

Disabled > Default
 Rising Gradient (modifica gradiente)
 Maintenance Time (modifica tempo)
 Rising Gradient and Maintenance Time (mod.entrambi)
 Falling Gradient (modifica gradiente in discesa)
 Rising and Falling Gradient (modifica gradiente in
salita e discesa)
 Falling Gradient and Maintenance Time

All (modifica tutti i parametri)
54  Visualization Type
imposta la visualizzazione sul display 1 e 2
 1 Process, 2 Setpoint > Default
 1 Process, 2 Hide dopo 3 sec.
 1 Setpoint, 2 Process.
 1 Setpoint, 2 Hide dopo 3 sec.
16
La visualizzazione del punto decimale dipende dall’impostazione del
parametro  e del parametro 
Manuale d’suo - ATR 142 109
55  Degree
selezione tipo gradi

Gradi Celsius > Default

Gradi Fahrenheit
56  Baud Rate
seleziona il baud rate per la comunicazione seriale






> Default
57  Slave Address
seleziona l’ID dello slave per la comunicazione seriale.
0 – 255 > Default: 254.
58  Serial Delay
seleziona il ritardo seriale
0 - 100 millisecondi > Default: 20.
59  Master
seleziona la modalità master.

Disable > Default
 Write Process
 Read Write Command Setpoint
 Write Output Percentage
 Read Write Alarm 1 Setpoint
 Read Process
60  Address Retransmission
seleziona l’indirizzo per la ritrasmissione
0x0000 – 0xFFFF esadecimale > Default: 0x03E9.
110 ATR 142 - Manuale d’uso
61  Lower Limit Retransmission
limite inferiore range ritrasmissione
-999 - 9999 [digit17], (gradi per sensori di temperatura) >
Default: 0.
62  Upper Limit Retransmission
limite superiore range ritrasmissione18
-999 – 9999 [digit19], (gradi per sensori di temperatura) >
Default: 0.
63  Timer Function
abilita 1 o 2 timer impostabili da menù utente e collegabili
agli allarmi.

Disable > Default
 Single Timer Seconds
 Double Timer Seconds
 Double Sequential Timer Seconds
 Double Timer Loop Seconds
 Single Timer Minutes
 Double Timer Minutes
 Double Sequential Timer Minutes
 Double Timer Loop Minutes
64  Falling Gradient
gradiente di discesa per ciclo preprogrammato
0 disabilitato (raffreddamento naturale) > Default: 0.
1-9999 gradi/ora con visualizzazione del decimo.
17
18
19
La visualizzazione del punto decimale dipende dall’impostazione del
parametro  e del parametro 
Se i parametri 61  e 62  hanno lo stesso valore, il valore
ritrasmesso non viene scalato.
La visualizzazione del punto decimale dipende dall’impostazione del
parametro  e del parametro 
Manuale d’suo - ATR 142 111
12
Modi d’intervento allarme
Allarme assoluto o allarme di soglia (selezione )
Pv.
Alarm Spv
Hysteresis
parameter
$+< > 0
Time
On
Off
On
Off
Alarm output
Allarme assoluto con regolatore in funzionamento caldo (Par.11  selezionato
) e valore di isteresi
maggiore di “0”
(Par.28  > 0).
NB: l’esempio è riferito all’allarme 1; la funzione è abilitabile
anche per l’allarme 2 sui modelli che lo prevedono.
Hysteresis
parameter
$+< < 0
Pv
Alarm Spv.
Time
On
Off
On
Off
Alarm output
Allarme assoluto con regolatore in funzionamento
caldo (Par.11  selezionato ) e valore di isteresi minore di “0” (Par.28
 < 0).
NB: l’esempio è riferito all’allarme 1; la funzione è abilitabile
anche per l’allarme 2 sui modelli che lo prevedono.
112 ATR 142 - Manuale d’uso
Time
Pv
Hysteresis
parameter
$+< > 0
Alarm Spv
On
Off
On
Off
Alarm output
Time
Pv
Alarm Spv
Hysteresis
parameter
$+< < 0
On
Off
On
Off
Allarme assoluto con regolatore in funzionamento
freddo (Par.11  selezionato ) e valore di isteresi maggiore di “0” (Par.28
 > 0).
Alarm output
Allarme assoluto con regolatore in funzionamento
freddo (Par.11  selezionato ) e valore di isteresi maggiore di “0” (Par.28
 > 0).
NB: l’esempio è riferito all’allarme 1; la funzione è abilitabile
anche per l’allarme 2 sui modelli che lo prevedono.
Allarme assoluto o allarme di soglia riferito al setpoint di
comando (selezione )
Command Spv
Allarme assoluto riferito al
Hysteresis
parameter
set di comando, con regola$+< > 0
tore in funzionamento caldo
Alarm Spv
(Par.11  selezionato
) e valore di isteresi
Time
maggiore di “0” (Par.28
On
Off
Off Alarm output
 > 0).
Il set di comando può essere variato con la pressione dei tasti
freccia da frontale o con comandi su porta seriale RS485.
Manuale d’suo - ATR 142 113
NB: l’esempio è riferito all’allarme 1; la funzione è abilitabile
anche per l’allarme 2 sui modelli che lo prevedono.
Allarme di Banda (selezione )
Pv
Allarme di banda valore di
Alarm Spv
isteresi maggiore di “0”
Hysteresis
Command Spv
parameter
(Par.28  > 0).
$+< > 0
Alarm Spv
NB: L’esempio è riferito
all’allarme 1; la funzione è
Off
Off
Off
Alarm output abilitabile anche per l’allarme 2 sui modelli che lo prevedono.
Time
On
On
On
Hysteresis
parameter
$+< < 0
Pv
Command Spv
Alarm Spv
Hysteresis
parameter
$+< < 0
Time
On
On
Off
On
Off
Allarme di banda valore di
isteresi minore di “0” (Par.28
 < 0).
Off
114 ATR 142 - Manuale d’uso
Alarm output
NB: L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per l’allarme 2 sui
modelli che lo prevedono.
Allarme deviazione superiore (selezione )
Pv
Alarm Spv
Hysteresis
parameter
$+< > 0
Command Spv
Time
On
Off
On
Off
Allarme
di
deviazione
superiore valore di setpoint
allarme maggiore di “0” e
valore di isteresi maggiore
di “0” (Par.28  > 0).
Alarm output
NB: a) L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per l’allarme 2 sui modelli che lo prevedono.
b) Con isteresi minore di “0” (  < 0) la linea tratteggiata si sposta sopra il Setpoint di allarme.
Pv
Command Spv
Alarm Spv
Hysteresis
parameter
$+< > 0
Time
On
Off
On
Off
Allarme di deviazione superiore valore di setpoint allarme minore di “0” e valore di
isteresi maggiore di “0”
(Par.28  > 0).
Alarm output
NB: a) L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per l’allarme 2 sui modelli che lo prevedono.
b) Con isteresi minore di “0” (  < 0) la linea tratteggiata si sposta sopra il Setpoint di allarme.
Manuale d’suo - ATR 142 115
Allarme deviazione inferiore (selezione )
Pv
Command Spv
Hysteresis
parameter
$+< > 0
Alarm Spv
Time
On
On
Off
Off
Allarme
di
deviazione
inferiore valore di setpoint
allarme maggiore di “0” e
valore di isteresi maggiore
di “0” (Par.28  > 0).
Alarm output
NB: a) L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per l’allarme 2 sui modelli che lo prevedono.
b) Con isteresi minore di “0” (  < 0) la linea tratteggiata si sposta sotto il Setpoint di allarme.
Hysteresis
parameter
$+< > 0
Pv.
Alarm Spv
Command Spv
Time
On
On
Off
Off
Allarme di deviazione inferiore valore di setpoint allarme minore di “0” e valore di
isteresi maggiore di “0” (Par.
28  > 0).
Alarm output
NB: a) L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per l’allarme 2 sui modelli che lo prevedono.
b) Con isteresi minore di “0” (  < 0) la linea tratteggiata si sposta sotto il Setpoint di allarme.
116 ATR 142 - Manuale d’uso
13
Tabella segnalazioni anomalie
In caso di mal funzionamento dell’impianto il controllore
spegne l’uscita di regolazione e segnala il tipo di anomalia
riscontrata.
Per esempio il regolatore segnalerà la rottura di un’eventuale
termocoppia collegata visualizzando  (lampeggiante)
sul display.
Per le altre segnalazioni vedi la tabella sottostante.
Cause
What to do
 Errore in programmazio- Chiamare Assistenza
 ne cella E²PROM.
Guasto sensore
temperatura giunto
 freddo o temperatura
Chiamare Assistenza
 ambiente al di fuori dei
limiti ammessi.
Dati di configurazione
Verificare che i parametri
 errati. Possibile perdita di configurazione siano
 della tarature dello
corretti.
strumento.
Controllare il collega Termocoppia aperta o
mento con le sonde e la
 temperatura fuori limite. loro integrità.
Controllare il
Fuori linea in caso di
 funzionamento master collegamento seriale,
il baud-rate e l’ID dei
 con processo remoto
moduli
 Taratura mancante

Chiamare Assistenza
Manuale d’suo - ATR 142 117
14
Promemoria configurazione
Data:
Installatore:
Note:
























Model ATR142:
Impianto:
Selezione tipo uscita di comando
Configurazione ingresso analogico
Seleziona il tipo di decimale visualizzato
Limite inferiore setpoint
Limite superiore setpoint
Limite inferiore range An1 solo per
normalizzati
Limite superiore range An1 solo per
normalizzati
Impostazione automatica dei limiti per
ingressi lineari.
Calibrazione offset
Calibrazione guadagno
Tipo di regolazione
Tipo di riarmo del contatto di comando
Stato del contatto per l’uscita di comando in
caso di errore.
Definisce lo stato del led OUT1
Isteresi in ON/OFF o banda morta in P.I.D.
Ritardo comando
Protezione del setpoint di comando
Banda proporzionale
Tempo integrale
Tempo derivativo
Tempo ciclo
Limite del segnale di comando
Selezione allarme 1
Contatto uscita allarme 1 e tipo intervento
118 ATR 142 - Manuale d’uso






























Tipo di riarmo del contatto dell’allarme 1
Stato del contatto per l’uscita di allarme 1
Stato del led OUT2
Isteresi allarme 1
Ritardo allarme 1
Protezione set allarme 1
Selezione allarme 2
Contatto uscita allarme 2 e tipo intervento
Tipo di riarmo del contatto dell’allarme 2
Stato del contatto per l’uscita di allarme 2
Stato del led OUT2
Isteresi allarme 2
Ritardo allarme 2
Protezione set allarme 2
Tipo di fluido refrigerante
Moltiplicatore di banda proporzionale
Sovrapposizione / Banda Morta
Tempo ciclo per uscita refrigerante
Filtro convertitore analogico
Frequenza di campionamento del
convertitore analogico
Filtro in visualizzazione
Selezione tipo autotuning
Deviazione dal setpoint di comando, per la
soglia tuning
Selezione funzionamento
Selezione automatico/manuale
Funzionamento ingresso digitale
Gradiente di salita per Soft Start
Tempo mantenimento per ciclo
Modificare gradiente e tempo di
mantenimento da utente
Selezione visualizzazione sui display
Manuale d’suo - ATR 142 119










Selezione tipo gradi
Seleziona il baud rate per la comunicazione
seriale
Seleziona l’indirizzo dello slave
Seleziona il ritardo seriale
Seleziona la grandezza da ritrasmettere
tramite ModBus
Seleziona l’indirizzo per la ritrasmissione
Limite inferiore range ritrasmissione
Limite superiore range ritrasmissione
Funzione Timer
Gradiente di discesa
Note / Aggiornamenti
120 ATR 142 - Manuale d’uso
Manuale d’suo - ATR 142 121
122 ATR 142 - Manuale d’uso
Read carefully the safety guidelines and programming instructions
contained in this manual before using/connecting the device
Prima di utilizzare il dispositivo leggere con attenzione le informazioni
di sicurezza e settaggio contenute in questo manuale
PIXSYS s.r.l.
www.pixsys.net
[email protected] - [email protected]
Software Rev 1.19
2300.10.092-G
061011
Scarica

ATR 142 - Grelci Maras