Operating Instructions Manual - ver.:1.1
Engine Digital Control controls and protects diesel engine. The device features 8 LED, 2 buttons, a key and 5 relay
output. Engine Digital Control manages oil pressure alarm, temperature alarm, fuel alarm, emergency stop and
battery charge alarm. Engine Digital Control permits normal manual star with the key or an automatic mode, by using
an external command.
Keyboard description
ENGINE DIGITAL CONTROL
Red LED – low oil pressare;
HIGH
TEMPERATURE
BATTERY
CHARGE
FAILURE
Red LED – battery charge failure;
LOW
OIL
PRESSURE
Red LED – high temperature;
LOW
FUEL LEVEL
Red LED – low fuel level;
OFF
Green LED– automatic startup;
E
HE
AUTO
PR
AT
PREHEAT
START
Red LED– engine stop;
STOP
Green LED– engine running;
ENGINE
RUNNING
Yellow LED– preheat;
Caratteristiche Tecniche
Power supply
Total output corrent
Start/preheat output current
Dimensions – DIN 96
Weight
Operating Temperature
Operating Humidity (not condensing)
9 Vdc up to 33 Vdc
5A @ 23°C (3,5A @ 60°C)
200mA @ 23°C each (130 mA @ 60°C)
96x96x61 (ex switch/key)
290 gr
-20°C / +70°C
95%
Dimensions
96 mm
90 mm
61 mm
ENGINE DIGITAL CONTROL
HIGH
TEMPERATURE
BATTERY
CHARGE
FAILURE
LOW
OIL
PRESSURE
OFF
ENGINE
RUNNING
START
STOP
PR
E
AT
HE
AUTO
PREHEAT
90 mm
96 mm
LOW
FUEL LEVEL
EN0534-C
1
ver.: 1.1
Collegamenti
CHARGER ALTERNATOR
POWER SUPPLY
D+
W.L.
B+
OUPUTS
FUEL
12V/24V
elettro stop
INPUT
battery charger
9
ALARM
OUTPUT
1
10
preheat
11
MAX 200mA
2
MAX 200mA
3
oil pressure switch
4
high temperature
5
emergency stop
6
fuel level
7
remote start
12
start
INPUT
13
power supply selection
8
key start output
15
30
+V
5A
14
preheat time
setting trimmer
50
not used – do not connect!
power supply selection
12V
24V
preheat time setting
Inputs
1 – battery charger (D+)
3 – oil pressure – N.C.
4 – temperature – N.A.
5 – emergency – N.A.
6 – fuel level – N.A.
7 – remote start– N.A.
15 – power supply – 12/24V
preheat
from 10 to 50 seconds
Outputs
2 – alarm
9 – fuel
10 – electric stop
11 – preheat – 200mA
12 – start – 200mA
14 – key manual start
Manual start:
A. turn the key clockwise until the first position "preheat"; all LEDs light up for test;
B. “Low oil pressure” and “preheat” LEDs light up; “preheat” LED stays lighted for a set time (from 10 to 50 seconds;
set with the rear trimmer);
C. As “engine running” LED starts to flash, turn the key to position "start", hold it till the engine stars and “engine
running” LED is steady lighted. If you do not turn the key within 15 seconds, "alarm" and "elettro stop" activate
and "fuel valve" disactivate.
D. to stop the engine, turn the key counter-clockwise till "off" position, press "stop" button or activate "emergency"
input (#5).
Low fuel level (input #6): "low fuel level" LED flashes and "alarm" outout (#2) is activated. After 5 minutes, if
there is no manual intervention , the device stops the engine and "low fuel level" remains lighted. After
refueling, you must first turn the key back to "off" in order to re-start the engine.
Low oil pressure (input #3): related LED lights up and the device stops the engine and activates "alarm"
output (#2). After refilling, you must first turn the key back to "off" in order to re-start the engine.
High temperature (input #4): “high temperature” LED lights up, the device stops the engine and activates
"alarm" output (#2). You must first turn the key back to "off" in order to re-start the engine.
ver.: 1.1
2
EN0534-C
Auto start:
A. turn the key clockwise until the first position "preheat"; all LEDs light up for test;
B. “Low oil pressure” and “preheat” LEDs light up; “preheat” LED stays lighted for a set time (from 10 to 50 seconds;
set with the rear trimmer);
C. Press “auto” button: “auto” LED starts flashing; as “remote start” is activated, the device makes 4 startup tries:
1. 4 seconds “start” #12 and “fuel” #9 are activated,
2. 3 seconds the device checks wheter the engine is running (oil pressure ok),
3. if engine is not running, it is stopped. Then starts the next try.
If after 4 tries the engine is still not running, the "alarm" output #2 and "electric stop" #10 are activated,
and "fuel" is deactivated.
E. to stop the engine, turn the key counter-clockwise till "off" position, press "stop" button or activate "emergency"
input (#5).
If “remote start” input #7 is deactivated, the device stops the engine by activating "electric stop" output
#10 and by deactivating "fuel" output #9; it then waits that “remote start” (#7) is reactivated: at this point it
repeats the auto start procedure.
High temperature (input #4): the device stops the engine by activating "electric stop" output #10 and by
deactivating "fuel" output #9; it then waits that temperature alarm goes off: at this point it repeats the auto start
procedure.
low fuel alarm (input #6): the device waits 5 minutes; then, if there is no manual intervention, It stops the
engine by activating "electric stop" output #10 and by deactivating "fuel" output #9.
Low oil pressure (input #3): the device stops the engine by activating "electric stop" output #10 and by
deactivating "fuel" output #9.
AUTO
EN0534-C
3
versione 1.1
LEDs and errors resume
the LED lights during preheating cycle.
PREHEAT
STOP
AUTO
ENGINE
RUNNING
the LED flashes indicating engine is stopping;
the LED lights up when engine has been stopped by pressing of "stop" button or by emergency input.
the LED falshes indicating that the device waits for an external start command; it then remains lighted
when the engine is running.
the LED flashes for 15 seconds indicating it waits a start command.
the LED remains lighted when engine is running.
indicates low oil pressure;
indicates high temperature:
manual start: engine is stopped;
automatic start: engine is stopped; when temperature alarm goes off the engine is restarted;
battery charge failure;
low fuel lever.
The CE marking of components does not
guarantee the compliance of the end product, and
does not absolve the manufacturer of the end
product from fulfilment of legal obligations.
Entity Elettronica s.r.l. publishes this manual without making any warranty as to the content herein. Entity
reserves the right to make modifications, additions and deletions to this manual due to typographical errors,
inaccurate information, or improvements to programs and/or equipment at any time and without notice.
Electronic design and manufacturing
via Dei Laghi, 36077
Altavilla Vicentina (VI),
tel.: 0444.57.44.88
fax: 0444.37.04.82
www.entityel.it - [email protected]
Scarica

Keyboard description Caratteristiche Tecniche Dimensions