SPECIFICA CONNESSIONI IN SITO - ON SITE CONNECTION DETAILS
1. ELETTRICA - ELECTRICAL
Tipo - Type:
STANDARD
Tensione - Voltage:
400V / 3~+N+PE / 50Hz
Potenza - Power:
6,05 kW / 14 A
Fusibili - Fuse rating:
3 x 16 A
Cavo e sezione min. - Cable and min. section:
Colori dei cavi - Cable colours:
L1: Nero - Black
L2: Grigio - Gray
L3: Marrone - Brown
N: Blu - Blue
PE: Giallo/Verde - Yellow/Green
2. ACQUA DI ALIMENTO - FEED WATER
Connessione - Connection:
Portata max. - Max. flow rate:
Pressione dinamica min. - Min. flow pressure:
Pressione max. - Max. pressure:
Temperatura max. - Max. temperature:
Durezza max. - Max. hardness:
3/4" maschio-male - DN20
25 lt/min
200 kPa (2,0 bar g)
300 kPa (3,0 bar g)
n.a. / 5...8 pH
40 mg/l
Residuo solido max. - Max. TDS
Contamin. max.-Max. pollution grade
3. ARIA COMPRESSADI PROCESSO- COMPRESSED AIR PROCESS
Connessione - Connection:
1/8" maschio-male
Portata max. - Peak flow rate:
Pressione - Supply pressure:
200...800 kPa (2..8 bar g)
Contaminazione max. - Max. pollution
Olio residuo max. - Max. rest oil
Vapore acquo max.- Max. water vapour
67 ppm
Temp. rugiada max. - Max. dewpoint temperat.
4. ARIA COMPRESSA TECNICA- TECHNICAL COMPRESSED AIR
1/4" maschio-male
Connessione - Connection:
Portata max. - Peak flow rate:
Pressione -Supply pressure:
600...800 kPa (6..8 bar g)
5. SCARICO PRINCIPALE - MAIN DRAIN
Connessione - Connection:
Portata max. - Peak flow rate:
Altezza max. - Max. height:
Temperatura max. - Max. temperature:
6. SFIATO CAMERA - EXHAUST AIR
Connessione - Connection:
Portata max. - Peak flow rate:
Pressione - Pressure:
1"-1/2 - DN40
25 lt/min
0,6 m
0...700 Pa (0...7 mbar g)
7. INGRESSO PER VALIDAZIONE - VALIDATION PORT
Connessione - Connection:
1/2" maschio-male DN15
Diametro ingresso - Inlet diameter
ALTRE SPECIFICHE - OTHERS DETAILS
AMBIENTE - ENVIRONMENT
< 40 dB (A)
EMISSIONI DI CALORE - HEAT EMISSIONS
Max. nel locale-Max. in the room:
Max. dal vano tecnico-Max. in service room:
Max. dal cesto/oggetti-Max. from trolley/items:
PESI - WEIGHTS
Netto totale - Total Net:
Lordo totale - Total Gross:
Max all'uso - Max. on working:
Carico a pavimento - Floor load:
di acqua potabile, il sistema di drenaggio deve essere
collegato mediante un adeguato dispositivo di non ritorno.
- Tutte le connessioni dei servizi per la macchina devono
rispettare tutte le normative e pratiche locali applicabili.
- Il fabbricante si riserva il diritto di apportare modifiche al
prodotto che possono non essere riportate nel disegno.
- The machine shall be horizontally levelled.
- The electrical supply of each machine must be protected with
a ground fault interrupter (30 mA, "AC" type).
- Manual shut off valves are required adjacent to supply
connection points for all media.
- For all ducted exhausts prevent condensate backflow into the
machine. Pitch vent ducting and discharge condensate at
lowest point.
- If a steam condenser is supplied and connected to a potable
water supply, the machine should be connected to the
drainage system using a proper non-return device.
- All services connections to the machine must comply with all
applicable local codes and practices.
- The manufacturer reserves the right to make product changes
that may not be reported in the drawing.
252 daN (kg)
270 daN (kg)
310 daN (kg)
CONFIGURAZIONE - CONFIGURATION
A) Risc. in circolazione-Circulating heating type: E: ELETTRICO-ELECTRICAL
B) Risc. in asciugatura-Air drying heating type: X:N.A.
C) Risc. in taniche-Tanks water heating type:
X: N.A.
NOTE - NOTES
- La macchina deve essere livellata orizzontalmente.
- L'alimentazione elettrica di ogni macchina deve essere
protetta con un interruttore differenziale (30 mA, tipo "AC").
- Sono richiesti dei rubinetti/valvole manuali adiacenti alle
connessioni per tutti i fluidi.
- Per tutti gli scarichi canalizzati si deve prevenire il riflusso di
condensa nella macchina. Posizionare i condotti di sfiato e
280 W (240 kcal/h)
n.a.
400 W (345 kcal/h)
ACCESSORI INSTALLATI - INSTALLED OPTIONALS
NESSUNO - NONE
24
25-06-2014
Rev.
Data / Date
AGGIORNATI DATI ARIA COMPRESSA E SCARICO - DRAIN AND COPRESSED AIR UPDATE
Descrizione / Description
GA_A3_IT-EN Rev_03
Descrizione/Description:
Dis./Drawn: Approv.:
PIANTA DI INSTALLAZIONE / INSTALLATION PLANT
Modello / Model:
Il presente documento
di proprieta' della STEELCO spa,
esso costituisce un bene di rilevante valore economico e non
puo' essere trasmesso e comunque divulgato a terzi senza
specifica autorizzazione scritta della Direzione STEELCO.
This document is the property of STEELCO spa, it is an asset
of considerable economic value and can not be transmitted
and otherwise divulged to third perties without specific written
permission of the Directorate STEELCO.
Franzato S. Capovilla I.
Revisione / Revision: Data / Date: Scala / Scale:
EW 2/1 (6,05kW 400V 50Hz - EXX version)
Codice cliente / Customer code:
--
Progetto / Project:
STANDARD
Ingegneria / Engineering:
STEELCO
24
25-06-2014
Rif. ordine / Order ref.:
--
--
1:25
Scarica