DVH 5241 (65A) / DVH 5261 (100A)
CONTATORE DI ENERGIA TRIFASE A INSERZIONE DIRETTA / 3-PHASE kWh METER DIRECT-CONNECTION
USCITA IMPULSI / PULSE OUTPUT - MID CLASS C (0,5%)
230Vac
1
3
4
6
7
9
11
Tar
L1’
L2’
L3’
N’
L1
L2
L3
N
13
15 Ingresso tariffa
Tariff input
Rete 4 Fili / 4 Wires Network
1
3
4
6
7
9
L1
N
20
SO
21 Uscita impulsi
23
Com
25 Comunicazione Modbus
Pulse output
11
L1’
N’
Rete 2 Fili / 2 Wires Network
Modbus Communication
SCHEMI DI COLLEGAMENTO
WIRING DIAGRAMS
CARATTERISTICHE TECNICHE
DVH 5241-65A
DVH 5261-100A
TENSIONE
Tensione nominale
3 x 230 / 400 V (-20 % / +15%)
Frequenza
50 Hz / 60 Hz
Potenza assorbita/dissipata
< 5VA / <2 W
CORRENTE
Tipo di ingresso
Trifase a inserzione diretta
Corrente nominale
10 A
Corrente massima
65 A
100 A
Corrente di start
40 mA
ACCURATEZZA
Classe C (MID)
Energia attiva
LED METROLOGICO
Numero impulsi
1000 impulsi/kWh
500 impulsi/kWh
Durata impulso
30ms
CIRCUITO DI INGRESSO TARIFFA
Tensione nominale
0 ... 230Vac
Tensione massima
265 Vac
USCITE STATICHE
Numero di uscite
1
Durata impulso
Range impostabile 30 ÷ 500 ms
Tensione massima
15 Vdc
Corrente massima
15 mA
INTERFACCIA SERIALE RS485
Protocollo
Modbus RTU Modbus ASCII
Baud-rate
Programmabile 300÷19200 bps
CONTENITORE
Esecuzione
6 moduli (DIN 43880)
Dimensioni meccaniche (mm)
105.4 x 96.2 x 65.86
Peso
520 g
Grado di protezione
IP 51
CONDIZIONI AMBIENTALI DI FUNZIONAMENTO
Installazione
Solo per uso interno
Temperatura d’impiego
-25°C … +55°C
Temperatura di stoccaggio
-25°C … +55°C
Ambiente meccanico
Class M2
Ambiente elettromagnetico
Class E2
Massima umidità d’impiego
75%
OMOLOGAZIONI E CONFORMITÀ
Conformità a norme
EN 50470-1, EN 50470-3
e l e t t ro n i c a
TECHNICAL CHARACTERISTICS
DVH 5241-65A
DVH 5261-100A
VOLTAGE
Nominal voltage
3 x 230 / 400 V (-20 % / +15%)
Frequency
50 Hz / 60 Hz
Power consumption/dissipation
< 5VA / <2 W
CURRENT
Input
Three-phase direct connection
Rated current
10 A
Max current
65 A
100 A
Starting current
40 mA
ACCURANCY
Active energy
Class C (MID)
METROLOGIC LED
Pulse number
1000 pulses/kWh
500 pulses/kWh
Pulse lenght
30ms
TARIFF COMMAND INPUT CIRCUI
Nominal voltage
0 ... 230Vac
Max voltage
265 Vac
STATIC OUTPUTS
Output number
1
Pulse lenght
Programmable range 30 ÷ 500 ms
Max voltage
15 Vdc
Max current
15 mA
RS485 SERIAL INTERFACE
Protocol
Modbus RTU Modbus ASCII
Baud-rate
Programmabile 300÷19200 bps
HOUSING
Version
6 modules (DIN 43880)
Mechanical dimensions (mm)
105.4 x 96.2 x 65.86
Weight
520 g
Degree of protection
IP 51
AMBIENT OPERATING CONDITIONS
Mounting
Indoor use only
Operating temperature
-25°C … +55°C
Storage temperature
-25°C … +55°C
Mechanical enviroment
Class M2
Electromagnetic enviroment
Class E2
Max operating humidity
75%
CERTIFICATIONS AND COMPLIANCE
Reference standards
EN 50470-1, EN 50470-3
ENERGY METERS FOR SINGLE-PHASE AND THREE-PHASE SYSTEMS MID APPROVED
| 5
Scarica

DVH 5241 (65A) / DVH 5261 (100A)