UG40
Energy Saving & Twin Cool units
Functioning and Adjustment
1
Energy Saving Units
Managing of free-cooling on Energy Saving units
Energy saving feature is done in the following way: the unit is water cooled; the water can be
cooled by a dry cooler or can be derived from a open or closet loop circuit.
2
Energy Saving Units
La regolazione dei radiatori esterni può avvenire:
•direttamente inviando un segnale al regolatore di velocità (è il caso di un DRY-COOLER non
UNIFLAIR);
•indirettamente inviando solo la commutazione del set-point al controllo indipendente della
RAL (è il caso del DRY-COOLER UNIFLAIR).
La regolazione diretta può essere a sua volta:
•modulante, secondo la rampa sotto disegnata;
•ON/OFF (per regolazione a due velocità).
La regolazione, sia “diretta” che mediante “commutazione del set-point”, può essere di due tipi:
•regolazione invernale, che interviene quando la differenza tra la temperatura ambiente e la
temperatura esterna supera i 9°C;
•regolazione estiva, che interviene quando tale differenza scende al di sotto dei 7°C.
3
Energy Saving Units
The microprocessor monitors both the ambient temperature and the ΔT between the water
temperature and the room temperature; its goal is to regulate the room temperature
according to the room temperature set-point and to maximize the energy saving effect.
Whenever the difference between the room temperature and the external temperature
(ambient temperature) is greater than 8.0±0.5°C, the microprocessor requires the maximum
cooling effect of the external radiators (this means that the CCU microprocessor changes
the dry-cooler’s set-point from “Summer Temp.” to “Temp. E.S.”).
Whenever the difference between the room temperature and the external temperature
(ambient temperature) is lesser than 7.0±0.5°C, the microprocessor regulates the external
radiators fans to optimize their operation in DX stage (the dry-cooler works with the
“Summer Temp.” set-point).
4
Energy Saving Units
The microprocessor also measures the inlet water temperature on the condenser side by an
NTC sensor; when the difference between the room temperature and the inlet water
temperature is greater than 6.5°C), it opens the 3-way valve in order to feed the free-cooling
coil (i.e. the ES mode has started).
Hence, according to the above mentioned points, the water temperature is controlled
according to two different temperature levels (with consequences on the regulation of the
dry-cooler’s fans) depending on the difference in temperature between the room temperature
and the external temperature.
5
Energy Saving Units
6
Energy Saving Units
7
Energy Saving Units
8
Energy Saving Units
9
Energy Saving Units
Uscita 7
10
Energy Saving Units
11
Energy Saving Units
12
Energy Saving Units
13
Energy Saving Units
14
Control Theory
15
16